RS485 INTERFACE (MODBUS RTU)

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

45

18

R

19

S

20

T

21

U

22

V

23

W

24

X

25

Y

26

Z

F16

16 bits

2’s COMPLEMENT SIGNED VALUE, 1 DECIMAL PLACE

<0

S2 Leads S1

>0

S1 Leads S2

F17

32 bits

UNSIGNED LONG VALUE, 3 DECIMAL PLACES

1st 16 bits

High Order Word of Long Value

2nd 16 bits

Low Order Word of Long Value

Example: 123456 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F18

32 bits

DATE MM/DD/YYYY

1st byte

Month 1 to 12

2nd byte

Day 1 to 31

3rd and 4th byte

Year 1995 to 2094

Example: Feb 20, 1995 stored as 34867147
i.e. 1st word: 0214, 2nd word 07CB
F19

32 bits

TIME HH:MM:SS:hh

1st byte

Hours 0 to 23

2nd byte

Minutes 0 to 59

3rd byte

Seconds 0 to 59

4th byte

Hundredths of seconds 0 to 99

Example: 2:05pm stored as 235208704
i.e. 1st word: 0E05, 2nd word 0000
F21

16 bits

2’s COMPLEMENT SIGNED VALUE, 2 DECIMAL PLACES

Power Factor

< 0

Leading Power Factor - Negative

> 0

Lagging Power Factor - Positive

Example: Power Factor of 0.87 lag is used as 87
i.e. 0057
F22

16 bits

TWO 8-BIT CHARACTERS PACKED INTO 16-BIT

UNSIGNED

MSB

First Character

LSB

Second Character

Example: String ‘AB’ stored as 4142 hex
F24

16 bits

UNSIGNED VALUE AS SECONDS SHOW AS Duration,

MAX VALUE = OFF

Example: 1234 stored as 1234, and displayed as 20 Mins
F25

16 bits

Trace Memory Channel Data

0

Leading

1

Lagging

Code

Type

Definition