COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

61

Bit 25

S2 CB Relay Lockout

Bit 26

Remote Timer Bypassed

Bit 27

S2 Remote Loadshed

FC197

16 bits

Number of Poles

0

Two Poles

1

Three Poles

2

Four Poles

FC198

16 bits

ATS Transfer Sequence

0

None

1

S1 to S2

2

S2 to S1

FC199

16 bits

ATS Transfer

0

None

1

S1

2

S1 Open

3

S2

4

S2 Open

5

Neutral

FC200

16 bits

ATS Present State

0

Load Connected to S1

1

Waiting to Start Gen

2

Starting Generator

3

Waiting for S2 OK

4

Waiting to Conn S2

5

Transferring to S2

6

Load Connected to S2

7

Waiting to Start Gen

8

Starting Generator

9

Load Connected to S2

10

Waiting to Conn S1

11

Transferring to S1

12

Waiting to Stop Gen

13

Stopping Gen

14

Test in Progress

15

S1 Failed. Checking S2

16

Waiting for In Phase

17

Sync Fail-Bypass Wait

18

Exerciser Count Down

19

Transferring to Center

20

Transferring to Center

21

Delayed Close on S1

22

Delayed Close on S2

23

Waiting to Conn S2

24

Waiting to Conn S1

25

Waiting to Close to S2

26

CT Open S1 after Xfer

27

Waiting to Close to S1

Code

Type

Definition