COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

63

FC308

16 bits

Frequency Status

0

None

1

Within Limit

2

Under Frequency Fail

3

Under Frequency Restore

4

Over Frequency Fail

5

Over Frequency Restore

FC309

16 bits

Voltage Status

0

None

1

Within Limit

2

Under Voltage Fail

3

Under Voltage Restore

4

Over Voltage Fail

5

Over Voltage Restore

FC311

16 bits

Phase Rotation Seq

0

1 Ph

1

ABC

2

ACB

3

- -

FC312

16 bits

Src No Of Phases

1

Single Phase

2

Three Phase

FC313

16 bits

Src Type

1

Utility

2

Generator

FC315

16 bits

ATS Status In Transfer Mode

0

None

1

S1 Failed

2

S2 Failed

3

Fast Test Load Xfer

4

Fast Test No Load Xfer

5

Test Load Xfer

6

Test No Load Xfer

7

Exerciser Running

8

Exerciser Bypassed

9

Exerciser Load Test

10

Exerciser No Load

11

ATS Lockout State

12

Shunt Fault Failure

FC316

32 bits

DATE MM/DD

1st byte

Month 1 to 12

2nd byte

Day 1 to 31

FC317

16 bits

Transfer type

0

Auto

1

Manual S1 to S2, S2 to S1 (S5)

2

Manual S2 to S1 Only (S5)

Code

Type

Definition