62

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

COMMUNICATIONS GUIDE

28

CT Open S2 after Xfer

29

Waiting for Reset key

FC201

16 bits

ATS Operating Mode

0

None

1

Normal

2

Test On Load

3

Test No Load

4

Exerciser On Load

5

Exerciser No Load

6

Fast Test

FC202

16 bits

Switch Position

0

On Generator

1

On Normal Src

FC212

16 bits

LCD Test Paint Color

0

None

1

Red

2

Green

3

Blue

FC300

16 bits

ATS Transfer Timer

0

None

1

P1Timer

2

P2 Timer

3

W Timer

4

T Timer

5

DW Timer

6

DT Timer

7

U1 Timer

8

U2 Timer

FC301

16 bits

ATS Elevetor Timer

0

None

1

W3

2

T3

FC302

16 bits

Exerciser Status

0

None

1

In Progress

2

Pending

3

Bypass

4

Cancel

5

Over

FC303

16 bits

Load Type

0

Gen Start And Xfer

1

Gen Start Only

FC306

16 bits

R50 Status

0

No Sync Status

1

Synchronized

2

Phasing In

3

Phasing Out

Code

Type

Definition

Advertising