COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

43

43437

0D6C

Reserved

---

---

---

---

---

---

1

43438

0D6D

CDT Event 22 Date

0

0X0C1F082E 1

---

FC316

0

2

43440

0D6F

CDT Event 22 Load

0

1

1

---

FC303

0

1

43441

0D70

CDT Event 23 Start Time

0

0X173B3B63 1

---

F19

0

2

43443

0D72

CDT Event 23 Duration

0

3600

1

---

F24

0

1

43444

0D73

Reserved

---

---

---

---

---

---

1

43445

0D74

CDT Event 23 Date

0

0X0C1F082E 1

---

FC316

0

2

43447

0D76

CDT Event 23 Load

0

1

1

---

FC303

0

1

43448

0D77

CDT Event 24 Start Time

0

0X173B3B63 1

---

F19

0

2

43450

0D79

CDT Event 24 Duration

0

3600

1

---

F24

0

1

43451

0D7A

Reserved

---

---

---

---

---

---

1

43452

0D7B

CDT Event 24 Date

0

0X0C1F082E 1

---

FC316

0

2

43454

0D7D

CDT Event 24 Load

0

1

1

---

FC303

0

1

43455

0D7E

Reserved

---

---

---

---

---

---

1

to

to

Reserved

---

---

---

---

---

---

1

43462

0D85

Reserved

---

---

---

---

---

---

1

ANALOG ALARM SETTINGS

43463

0D86

Voltage THD Alarm Level

1

1001

1

%

F2*

1001

1

43464

0D87

Voltage THD Alarm Delay

0

65535

1

s

F1

0

1

43465

0D88

Current THD Alarm Level

1

1001

1

%

F2*

1001

1

43466

0D89

Current THD Alarm Delay

0

65535

1

s

F1

0

1

43467

0D8A

Low PF Lag Alarm Level

0

100

1

---

F3*

100

1

43468

0D8B

Low PF Alarm Delay

0

65535

1

s

F1

0

1

43469

0D8C

Overpower Alarm Level

1

50001

1

kW

F2*

50001

1

43470

0D8D

Overpower Alarm Delay

0

65535

1

s

F1

0

1

43471

0D8E

Phase A Overcurrent Level

1

201

1

%FLA

F1*

201

1

43472

0D8F

Phase A Overcurrent Delay

0

65535

1

s

F1

0

1

43473

0D90

Phase B Overcurrent Level

1

201

1

%FLA

F1*

201

1

43474

0D91

Phase B Overcurrent Delay

0

65535

1

s

F1

0

1

43475

0D92

Phase C Overcurrent Level

1

201

1

%FLA

F1*

201

1

43476

0D93

Phase C Overcurrent Delay

0

65535

1

s

F1

0

1

43477

0D94

Neutral Overcurrent Level

1

201

1

%FLA

F1*

201

1

43478

0D95

Neutral Overcurrent Delay

0

65535

1

s

F1

0

1

43479

0D96

Low PF Lead Alarm Level

0

100

1

---

F3

*

100

1

*Maximum setpoint values represent OFF.

Modbus

Hex

Description

Min

Max

Step

Units

Format Default

Size in

Words