COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

57

Bit 28

Process ILock J Alarm

FC180

32 bits

Alarm Status 2

Bit 17

Self Test Alarm

Bit 18

Comm Fail Alarm

FC181

32 bits

Alarm Status 3

Bit 13

Bypass ATS on S2

Bit 14

Bypass ATS on S1

Bit 15

S1 OK

Bit 16

S2 OK

Bit 17

Voltage Diff > 5%

Bit 18

Low Power Factor

Bit 19

Overpower kW

Bit 20

Phase A Overcurrent

Bit 21

Phase B Overcurrent

Bit 22

Phase C Overcurrent

Bit 23

Neutral Overcurrent

Bit 20

S1 to S2 Manual Xfer

Bit 21

S2 to S1 Manual Xfer

Bit 22

S1 Volt THD

Bit 23

S2 Volt THD

Bit 26

Current THD

FC182

32 bits

Alarm Status 4

Bit 0

CTAP Audible Alarm

Bit 1

S2 Shunt Fault

Bit 2

S1 Undervoltage

Bit 3

S1 Overvoltage

Bit 4

S1 Underfrequency

Bit 5

S1 Overfrequency

Bit 6

S2 Undervoltage

Bit 7

S2 Overvoltage

Bit 8

S2 Underfrequency

Bit 9

S2 Overfrequency

Bit 10

S1 Volt Imbalance Alarm

Bit 11

S2 Volt Imbalance Alarm

Bit 12

Inhibited via Disconnect Switch

Bit 13

Switch Exercising

Bit 14

Neutral Position

Bit 15

Xfer to Alternate Source

Bit 16

S1 to S2 Auto Xfer Alert

Bit 17

S2 to S1 Auto Xfer Alert

Bit 18

S1 to S2 Inhibit

Bit 19

S2 to S1 Inhibit

Bit 20

Engine Start

Bit 21

Auto Load Shed Active

Bit 22

Not in Auto

Bit 23

S1 Failure

Bit 24

Alternate Source Fail to Start

Code

Type

Definition