GE Industrial Solutions MX350 Communications Guide User Manual

Page 28

Advertising
background image

24

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

COMMUNICATIONS GUIDE

32130

0851

Time To ShutDown Gen

---

---

---

---

F24

N/A

1

32131

0852

Date Gen Start Sent

---

---

---

---

F18

N/A

2

32133

0854

Time Gen Start Sent

---

---

---

---

F19

N/A

2

32135

0856

Date Gen Stop Sent

---

---

---

---

F18

N/A

2

32137

0858

Time Gen Start Stop

---

---

---

---

F19

N/A

2

32139

085A

Gen Supply OK Date

---

---

---

---

F18

N/A

2

32141

085C

Gen Supply OK Time

---

---

---

---

F19

N/A

2

32143

085E

Alt Source Startup Time

---

---

---

s

F1

N/A

1

32144

085F

Max Alt Source Volt THD

---

---

---

%

F1

N/A

1

32145

0860

Time Gen Start Removed

---

---

---

---

F19

N/A

2

32147

0862

Reserved

---

---

---

---

---

---

1

ATS R50

32148

0863

In Phase Monitor Status

---

---

---

---

FC306

N/A

1

32149

0864

Reserved

---

---

---

---

---

---

1

32150

0865

S1 S2 Phase A Difference

---

---

---

°

F16

N/A

1

32151

0866

Reserved

---

---

---

---

---

---

1

32152

0867

Reserved

---

---

---

---

---

---

1

32153

0868

Reserved

---

---

---

---

---

---

2

32155

086A

Reserved

---

---

---

---

---

---

1

32156

086B

Reserved

---

---

---

---

---

---

1

32157

086C

Reserved

---

---

---

---

---

---

1

32158

086D

Reserved

---

---

---

---

---

---

1

ATS S1 COUNTERS

32159

086E

Total Primary Source Failures

---

---

---

---

F1

N/A

1

32160

086F

S1 Accum. Avail.

---

---

---

hrs

F9

N/A

2

32162

0871

S1 Accum. Unavail.

---

---

---

hrs

F9

N/A

2

32164

0873

S1 Avail. Since Last Restore

---

---

---

hrs

F9

N/A

2

32166

0875

S1 Last Unavail. Time

---

---

---

hrs

F9

N/A

2

32168

0877

Last Primary Source Fail Date

---

---

---

---

F18

N/A

2

32170

0879

Last Primary Source Fail Time ---

---

---

---

F19

N/A

2

32172

087B

S1 Date Stamp Last Restore

---

---

---

---

F18

N/A

2

32174

087D

Time Primary Ret (or Test

Reset)

---

---

---

---

F19

N/A

2

32176

087F

Last Transfer to S1 Date

---

---

---

---

F18

N/A

2

32178

0881

Last Transfer to S1 Time

---

---

---

---

F19

N/A

2

32180

0883

Reserved

---

---

---

---

---

---

1

32181

0884

Reserved

---

---

---

---

---

---

1

ATS S2 COUNTERS

32182

0885

Number of S2 Failures

---

---

---

---

F1

N/A

1

32183

0886

S2 Accum. Avail.

---

---

---

hrs

F9

N/A

2

32185

0888

S2 Accum. Unavail.

---

---

---

hrs

F9

N/A

2

32187

088A

S2 Avail. Since Last Restore

---

---

---

hrs

F9

N/A

2

32189

088C

S2 Last Unavail. Time

---

---

---

hrs

F9

N/A

2

32191

088E

S2 Date Stamp Last Fail

---

---

---

---

F18

N/A

2

32193

0890

S2 Time Stamp Last Fail

---

---

---

---

F19

N/A

2

32195

0892

S2 Date Stamp Last Restore

---

---

---

---

F18

N/A

2

Modbus

Hex

Description

Min

Max

Step

Units

Format Default

Size in

Words

Advertising