MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

COMMUNICATIONS GUIDE

Bit 25

S1 Disconnected

Bit 26

S2 Disconnected

Bit 27

S1 Connected

Bit 28

S2 Connected

Bit 29

Freqs Differ > 0.2Hz

Bit 30

Test Initiated

Bit 31

R15 / Disconnect from S2

FC183

32 bits

Fault Status 1

Bit 0

Any Fault

Bit 17

Comm Fail Fault

Bit 18

Relay Not Configured

Bit 19

Process ILock A Fault

Bit 20

Process ILock B Fault

Bit 21

Process ILock C Fault

Bit 22

Process ILock D Fault

Bit 23

Process ILock E Fault

Bit 24

Process ILock F Fault

Bit 25

Process ILock G Fault

Bit 26

Process ILock H Fault

Bit 27

Process ILock I Fault

Bit 28

Process ILock J Fault

FC184

32 bits

Fault Status 2

Bit 13

S1 & S2 Fail to Open

Bit 14

Phase Rotation Error

Bit 15

Sources Out of Phase

Bit 16

S1 Lmt Sw Not Closed

Bit 17

S1 Lmt Sw Not Opened

Bit 18

S2 Lmt Sw Not Closed

Bit 19

S2 Lmt Sw Not Opened

Bit 20

S1 Del Lmt Sw Not Closed

Bit 21

S1 Del Lmt Sw Not Opened

Bit 22

S2 Del Lmt Sw Not Closed

Bit 23

S2 Del Lmt Sw Not Opened

FC185

32 bits

Fault Status 3

Bit 8

ATS Lockout

Bit 9

S1 Failure to Disconnect

Bit 10

S2 Failure to Disconnect

Bit 11

S1 Failure to Connect

Bit 12

S2 Failure to Connect

Bit 13

S1 & S2 Fail to Disconnect

Bit 14

Phase Rotation Error

Bit 15

Sources Out of Phase

Bit 16

S1 Lmt Sw Not Closed

Bit 17

S1 Lmt Sw Not Opened

Bit 18

S2 Lmt Sw Not Closed

Bit 19

S2 Lmt Sw Not Opened

Bit 20

S1 Del Lmt Sw Not Closed

Code

Type

Definition