GE Industrial Solutions GERAPID 2508, 4008, 5008, 6008 WITH ARC CHUTE 1X2 User Manual

Page 13

Advertising
background image

2011-03-14 S47183De rev.01

Design and specifications are subject to change without notice

13

3.4 Control circuits data

Control box terminals

1x12-pole

AC 400 V, 20 A

4x15-pole

AC 250 V, 8 A

Closing solenoid drive

1)

Rated voltage

AC 120 V, 230 V and DC 125 V, 250 V

Operating range

80 % - 115 % of rated voltage

Power consumption Gerapid 2508 / 4008

1750 W / 2000 W

Power consumption Gerapid 5008 / 6008

2600 W / 2600 W

Minimal CLOSING command duration

100 ms

min.interval between two "CLOSE" operations

~8 s w/o NEKO installed; ~14 s with NEKO

Internal voltage converter

1)

Input: Voltage range

DC 88 - 145 V

for Gerapid 2607, 4207, 6007, 8007

Output: Voltage range

DC 24 V (±5%)

Current

6 A permanent

Model description

PCMD 150 110 S24W-GE

Input: Voltage range

AC 115 - 240 V, DC 125 - 353 V

Output: Voltage range

DC 24 V (±5%)

Current

3 A permanent, 5 A/100 ms

Model description

PCMA 70 S24W-GE

Aux. contact HS 1…HS 8,

Rated operational voltage Ue/AC

230 V

OC trip target

Rated operational current Ie/AC-15

1 A

Arc chutes indicator

Conventional thermal current Ie/AC-12 (Ith)

10 A

Rated operational voltage Ue/DC

110 V / 220 V

Rated operational current Ie/DC-13

0.5 A / 0.3 A

Minimum current/voltage ratings

0,1 mA / 6 V DC

Contact duty (min. value)

DC 10 V / 2 mA

Shunt trip standard

Rated voltage/power Uc/Pc

24 V / 100 W

Operating range: OFF

21.6 V - 26.4 V

Shunt trip double winded

Rated voltage/power Uc

DC 125 V/ DC 220 V

Rated power for a single winding Pc

230 W

UVR

Rated voltage Uc

24 V

(Zero voltage release)

Operating range: OFF

< 4 V

Operating range: ON

24 V (±10%)

Power consumption

~ 10 W

ED impulse release

Required C-bank capacity

2000 µF

Charging voltage

300 V

Switching interval

max. 2/min with 10 consecutive operations

Endurance

1 000 operations with 1 operation per 180 s

Firing signal level / duration

6 - 24 V / 100 - 1000 ms

Charging signalization relay AC duty AC 250 V/ 0.5 A - AC 120 V /1 A

DC duty : DC 220V/0.1A - DC 125V/0.3A - DC 10V/3A

1)

Standard ambient conditions acc. to EN 50123-1 Attachement B. For meeting outside of this standard range, please call back.

Table 2a: Technical data of auxiliary circuits

Components

Technical datas of control circuits
Us / In

SU-Control

CLOSE-push-button -S1

DC 24 V / approx. 10 mA

ST releasing

push-button-S2

DC 24 V / approx. 4 A short time

UVR releasing

push-button -S2 ( -X2 :6 / :7)

DC 24 V / approx. 10 mA

push-button -S2 ( -X2 :8 / :9 )

DC 24 V / approx. 450 mA

ED-coil tripping w/o NEKO

push-button -S3

DC 300 V / 750 A / 3 ms

ED-coil tripping with NEKO

Connect "Firing signal" at ( -X2 :10 / :11 )

DC 6 V…24 V / approx.20 mA

Table 2b: Control circuits ( directional values to rate the components )

Advertising