6.2.2 Layout of control PCB inside control box
Fig. 53 Control box inside.
Slot Control board
Z-No.
Orientation
1
-
-
-
2
NEKO unit (ED trip)
128 750 R1
equipment to left
3
Voltage converter
128 730 R2-R4 equipment to left
4
SU-control unit
128 700
equipment to right
5
-
-
-
6
ST/UVR control unit
128 710 R1, R2
equipment to left
Table 5 Layout of control PCBs inside the control box.
Fig. 54 Control box front view
Warning: The isolation plates between the control boards
and at the wall of the box must always be present!
Hint: In older systems, the control boards may be installed
turned 180 °!
6.2.4 Replacement of the control boards
1. OPEN the breaker.
2. Disconnect power supply, and pull out all
the plugs from control box’s terminals.
3. If a NEKO control unit is installed, wait 1
minute until capacitors discharge.
Fig. 55-1 Unscrew and remove all the external plugs
Fig. 55-2 Unscrew four bolts of the box cover
Fig. 55-3 Carefully lower the box cover