4.3.3 NEKO control circuit

 Firing signal at (-X2 :10/:11) is processed by opto-coupler. Pay attention to the polarity!

 Closing STOP signal is provided to lock CLOSE command, until capacitors are fully charged.

 Be sure that voltage level is between DC 6 V - 24 V and there are no transient spikes (<3 ms) on firing signal. This

can lead to major defect of the NEKO control unit!

Maximum duration of the firing command must not exceed ~1 sec. Longer signal might cause NEKO failure! It is

recommended to use one of HS auxiliary contacts connected in series with firing circuit (-X2 :10). It will

automatically cut off the firing circuit after breaker opening.

Fig. 25 ED coil with internal NEKO control unit