GE Industrial Solutions GERAPID 2508, 4008, 5008, 6008 WITH ARC CHUTE 1X2 User Manual

Page 23

Advertising
background image

2011-03-14 S47183De rev.01

Design and specifications are subject to change without notice

23

4.3.6 Zero voltage release control circuit






















 The closing STOP signal is provided for resetting K2 on the SU-control circuit. It effects with priority in switching

OFF (by ST or UVR) before switching ON. Once switching ON and OFF signals are simultaneous, switching OFF

command will stay longer than switching ON. This means the OFF command is master command.

 -S2 (-X2 :6/:7) is NO contact, utilized for indirect releasing of the UVR by relay -K2

 -S2 (-X2 :8/:9) is NC contact utilized for direct releasing of the UVR. If it’s not used, please short this connection

permanently.

Fig. 28 UVR control circuit

Key position - 5

Key number - 00: Without shunt trip or zero voltage release.
Key number - 20: With zero voltage release.

36/ _ _ _ X _ _ _

1

2

3

4

5

6

8 (+)

7 (-)

9

10

-X10/X11: PCB

-X14 : UVR PCB

9 (+)

7 (-)

24VDC

External Trip

Signal, N.C.

Contact

Internal Close Stop

Interlocking To

Other PCBs

UVR Coil

Undervoltage Relea

s

e

D

e

v

ice

Pr

in

te

d

C

ir

c

u

it

B

o

ar

d

Breaker

PCB - Printed Circuit Board

Zero Voltage Release Circuit

- User external connection point

- Factory internal connection point

-X2:

9

8

External Trip

Signal, N.O.

Contact

7

6