2011-03-14 S47183De rev.01

Design and specifications are subject to change without notice

47

6.2 List of maintenance tasks

TYPE OF THE WORK

BY WHOM

WHEN REQUIRED

RECOMMENDATIONS

A.

Arc chute changing

-Customer

-Trained technician

As a result of the inspection C

B.

Arcing contact and arc

runners changing

-Customer

-Trained technician

As a result of the inspection C

Replace complete arcing set.

C.

Protective walls changing

-Customer

-Trained technician

As a result of the inspection C

D.

Adjustment of the

contacts

-GE Service Engr

As a result of the inspection C

Only when replacement of the arcing

contact results with incorrect gaps.

See point 6.1.5.

E.

Replacement of the

control board

-Customer

-Trained technician

As a result of the inspection B,E

F.

Adjustment of the

mechanism

-GE Service Engr

As a result of the inspection B,E

G.

Flexband or fixed contact

changing

-GE Service Engr

As a result of the inspection C,E

H.

Mechanism changing

-GE Service Engr

As a result of the inspection B,E

I.

Trip unit changing &

adjustment

-GE Service Engr

As a result of the inspection B,E

J.

Auxiliary contacts

adjustment and changing

-Customer

-Trained technician

As a result of the inspection B,E

In case of improper operation of the

switches, adjustment might be
necessary.

K.

Drive changing

-GE Service Engr

As a result of the inspection B,E

L.

Accessories changing

-GE Service Engr

As a result of the inspection B,E

Table 4


Required tools:

Cleaning tissue

Pocket lamp

Hand lever

Hexagon wrench SW 4, SW 5, SW 6

Screw wrench SW 10, SW 13

Torx® wrench size 30, 40 and 45

Small and medium screwdriver

Pliers

Wire cutter

File

Steel brush

Safety hints:

Securing against falling parts

Hint 1

Place a cloth into the lower area of the arcing

contact [Fig. a]. Remember to secure the closing drive

according to Hint 3.

Fig. a Protecting of the arcing area against falling parts

Maintenance with zero voltage release

Hint 2

If an optional zero voltage release is installed, it

must be energized to enable closing of the breaker. Only

then maintenance of the arcing contacts is possible.

Hint 3

To prevent the risk of injury, it is recommended

to secure the breaker in the closed position with a simple

mechanical interlock device [Fig. b]. A piece of tubing

having ~50 mm [~2 in] length and inner diameter of

minimum 14 mm [0,55 in] works well. The outer diameter

of the locking rod shall be less 8 mm [0,3 in]. GE does not

offer this locking device.


Fig. b Securing closing drive against opening