5.1 Safety distances.
Units call in mm (inches)
Legend for dimensional drawings
K
Heat sink (for Gerapid 6007)
L
Ventilation openings in the breaker cubicle top cover shall not be less than 50% of total surface area.
M
Solenoid closing drive
P
Diameter 9 mm [0,35 in], Countersunk screw M8
S
Control box
Z
Main Connector
Sa fety d istan ces - To Insu la ted Su rfa ces.
Unit s in mm (inch es)
Ty pe
Arc c hute
Main-
Addi tional
D eflect or
Gerapi d
Connecti on
is ol ation
E
A
B
C
D
2508 / 4008
1x2
H or V
10 (0.4)
700 (27.6)
150 (5.9)
150 (5.9)
120 (4.7)
5008
1x2
V / V with heat sinks
10 (0.4)
1000 (39.4)
300 (11.8)
300 (11.8)
180 (7.1)
6008
1x2
V / V with heat sinks
10 (0.4)
1000 (39.4)
300 (11.8)
300 (11.8)
180 (7.1)
H…Hor izontal term inal V...Vertical ter minal
Sa fety d istan ces - To Gr ounded Su rfac es .
Unit s in mm (inch es)
Ty pe
Arc c hute
Main-
Deflector
Gerapi d
Connecti on
E
A
B
C
D
2508 / 4008
1x2
H or V
10 (0.4)
1000 (39.4)
300 (11.8)
300 (11.8)
300 (11.8)
Safet y distan ces - Grounded Surfaces
Safety dist ances - Insulated Surfaces