4.3.2 Breaker Internal Control Power Supply























Fig. 23 Supply with voltage converter or with direct external 24 V DC ±5%.

1 (+)

3 (-)

-X3

4 (+ or ~)

5 (- or N)

+24VDC +/- 2%

to other PCBs

-X10: PCB

User Supplied

Control Power

Source

115-240VAC +/- 10%

or

35-350VDC +/- 10%

8

9

10

6

7

Ground

1 (+)

3 (-)

-X3

4 (+)

5 ( - )

+24VDC +/- 2%

to other PCBs

-X11: PCB

User Supplied

Control Power

Source

24VDC +/- 5%

8

9

10

6

7

Ground

Breaker

Breaker

- User external connection point

- Factory internal connection point

PCB - Printed Circuit Board

Breaker Internal Control Power Supply

User Supplied

Control Power

Source

115-240VAC +/- 10%

or

88-350VDC +/- 10%

Breaker Internal Control Power Supply (UL)