3.3.6 Connecting additional external batteries (8/10 kVA models)


In case of additional external battery packs, batteries are shipped separately from the battery cabinet.
They have to be mounted inside the cabinet after battery installation. Please proceed with the following
steps:

fig. 3.3.6.a

1. Unpack the 2 battery packs from

their carton box.

2. Place the battery packs side by

side in the battery compartment
(2, fig. 3.3.6.a).

3. Fix the 2 battery brackets with

the screw set to hold battery
packs into the cabinet
(3, fig. 3.3.6.a)

4. Connect the DC connectors of

each battery pack (4, fig. 3.3.6.a).

5. Fix the battery grille in front of

the battery compartment with 3
screws (5, fig. 3.3.6.b).

6. Mount the 2 battery front covers.

(6, fig. 3.3.6.b).

fig. 3.3.6.b

8/10 kVA

8/10 kVA


The additional external battery pack connects to the UPS in the same way whether the UPS is being
used in tower or rack mount format. When used in tower format, the UPS and additional battery packs
can be mounted together in one set of mounting support stands (fig.3.3.6.c).

Connect the cables provided with the battery between UPS and battery pack – plug them between UPS
sockets and nearest sockets on the battery pack (fig.3.3.6.d). The connectors and sockets are keyed and
can be plugged only in correct position. At first start up the value of the total battery capacity has to be
set with the UPS Monitoring software.

fig. 3.3.6.c

fig. 3.3.6.d

8/10 kVA

8/10 kVA

modifications reserved

14

User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)