Internal battery replacement (for 5/6 kva models), 5/6 kva – GE Industrial Solutions Digital Energy GT Series UPS 5_6_8_10 kVA User Manual

Page 37

Advertising
background image

7.4.1 Internal battery replacement (for 5/6 kVA models)


In case of battery failure, please proceed with the following steps to replace that:

NOTE

During battery replacement the UPS will not be able to support the load if a mains

failure occurs! It is recommended to switch off the load

(see section 4.3.2) before

battery manipulation

.



1. Remove the UPS front cover

from the cabinet by gently
pulling it out.

2. Remove the battery grille by

loosening the two mounting
screws (fig. 7.4.1.a).

3. Grab hold of the battery pack

and slide it out (fig. 7.4.1.b).
Be careful during this
operation and consider the
weight of the battery.

4. Unpack the new battery pack

from its carton box.

5. Place the battery pack in

front of the battery
compartment, aligning the
rear connector to the front
panel (see section 3.3.3).

6. Slide the battery pack into

the battery compartment
until the rear connector is
plugged with the UPS
internal DC socket.

7. Fix the battery grille by

tightening screws.

8. Mount the two front covers.

fig. 7.4.1.a

fig. 7.4.1.b

5/6 kVA

5/6 kVA


NOTE

To avoid battery malfunction, in case of additional batteries connected, all battery packs
have to be replaced! It’s not possible to replace only 1 pack. Avoid connection between
new and old battery packs.

modifications reserved

37

User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)