8 TROUBLESHOOTING



Whenever a malfunction occurs, first check external factors (e.g. connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see fig. 3.3.5.a/b) and be sure that the
UPS is not overloaded.


The following chart is a simple troubleshooting checklist. If the suggested solution does not succeed, or if
the information is insufficient to solve the problem, please contact your dealer or consult
www.GEDigitalEnergy.com


PROBLEM

POSSIBLE CAUSE

SOLUTION

Mains switched off

Switch on mains supply

No mains voltage present

Carry out mains inspection,
consult qualified electrician

No display
No alarm
(UPS switched off)

Input fuse blown or circuit
breaker tripped

Replace fuse or reset breaker

Mains indicator not illuminating,
acoustic alarm intermittent

No mains voltage present

Read section 4.4.2 – UPS on
battery

Mains indicator not illuminating,
mains voltage present, acoustic
alarm intermittent

Input fuse blown or circuit
breaker tripped

Replace fuse or reset breaker

UPS failure

Contact UPS dealer or go to
www.GEDigitalEnergy.com

UPS over-temperature

Allow UPS to cool down

Alarm LED illuminated,
continuous acoustic alarm

Overload at UPS output

Reduce UPS load

Battery extension fuse switch is
in ‘Open’ position

Switch to ‘On’ position

Batteries are not fully charged

Charge batteries for 8 hours and
reconfirm runtime

Batteries are defective

Contact UPS dealer

Delivered runtime less than
specified

Charger is defective

Contact UPS dealer

Last load bar LED is lit, acoustic
alarm intermittent

Overload at UPS output

Reduce UPS load

Incorrect communication cable

Check whether correct cable is
used

PC interface defective or being
accessed by another service

Check if no other software is
accessing the interface

No communication between
UPS and PC

Interference on the data cable

Rearrange cables

modifications reserved

40