Page 34: 5/6 kva pdus, 8/10 kva pdus, Extended runtime

Advertising
background image

6.1.1 5/6 kVA PDUs

Model

Outlets (NEMA)

Inlets (NEMA)

TB

5-20R T

L5-20R

L5-30R

EN60320

L6-20R

L6-30R

L14-30R TB L14-30P

L1-N-G L2-N-G L1-N-G L2-N-G L1-N-G L2-N-G L1-N-G L2-N-G

L1-L2-G

L1-L2-G

L1-N-L2-G

GT PDU A 01*

1

1

GT PDU A 02

1

1

GT PDU A 03

2

2

1

1

1

GT PDU A 04

1

1

2

1

GT PDU A 05

2

2

2

1

GT PDU A 06

2

2

1

GT PDU A 07

2

2

1

1

1

GT PDU A 08

2

2

2

1

GT PDU A 09

4

1

*: No 3 pole 6 ms maximum transfer time manual bypass

6.1.2 8/10 kVA PDUs

Outlets (NEMA)

Model

5-20R T-type

L5-20R

L6-20R

L6-30R

L1-N-G

L2-N-G

L1-N-G

L2-N-G

L1-L2-G

L1-L2-G

GT PDU B 01

4

4

2

GT PDU B 02

2

2

4

GT PDU B 03

2

2

4

GT PDU B 04

2

2

2

2

GT PDU B 05

2

2

1

1

2

GT PDU B 06

2

2

4


6.2 EXTENDED RUNTIME

Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In this
case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of
the available runtime (via UPS monitoring software). Depending of the charge condition of the new
batteries the new runtime calculations may temporarily be unreliable.

Additional batteries increase the recharging time for the unit; all other operational information is the same
as for standard models. The following table shows runtimes with up to 3 Battery Packs. 1 Battery Pack is
the normal configuration.

Unit

Load

Internal Batteries

1 Battery Pack

2 Battery Pack

3 Battery Pack

10%

75 min

156 min

235 min

313 min

25%

31 min

75 min

115 min

155 min

50%

14 min

34 min

58 min

82 min

75%

8 min

22 min

35 min

50 min

GT5000 RT

100%

5 min

14 min

25 min

36 min

10%

75 min

156 min

235 min

313 min

25%

31 min

75 min

115 min

155 min

50%

14 min

34 min

58 min

82 min

75%

8 min

22 min

35 min

50 min

GT6000 RT

100%

5 min

14 min

25 min

36 min

10%

107 min

251 min

333 min

494 min

25%

40 min

100 min

160 min

225 min

50%

16 min

39 min

66 min

92 min

75%

10 min

24 min

41 min

58 min

GT8000 RT

100%

6 min

17 min

28 min

41 min

10%

107 min

251 min

333 min

494 min

25%

40 min

100 min

160 min

225 min

50%

16 min

39 min

66 min

92 min

75%

10 min

24 min

41 min

58 min

GT10000 RT

100%

6 min

17 min

28 min

41 min

modifications reserved

34

User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)