3 general, 4 transport / storage, General – GE Industrial Solutions Digital Energy GT Series UPS 5_6_8_10 kVA User Manual

Page 5: Transport / storage

Advertising
background image

1.3 GENERAL

DANGER! RISK OF ELECTRIC SHOCK.

The UPS has an internal battery supply with a nominal voltage of 144Vdc / 288Vdc.

Some of the parts of the UPS are necessarily under a hazardous voltage. Do not

open the unit; there are no user serviceable parts inside.

The appliance outlets and output terminals may be electrically live, even when the

UPS is disconnected from the mains.

CAUTION

There may be damage to the equipment if procedures and practices are not strictly

observed and followed.




1.4 TRANSPORT / STORAGE

NOTE

Check for sufficient floor and elevator loading capacity. Move the UPS and the
battery pack in its original package to the final destination room. Do not stack
other package on top.

WARNING!

Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS from

the pallet! Never try to lift the unit by yourself!


• No liability can be accepted for any transport damage when the equipment is shipped in non-original

packaging.

• Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature must be

within -20 +45 °C (-4°F and 113°F). If the unit is stored for a period exceeding 3 months, optimal battery
lifetime is obtained if the storage temperature does not exceed 30°C (86°F).

• If the unit is stored for an extended period of time, the batteries must be recharged periodically.

Connect the unit to a wall outlet and recharge the batteries for 24 hours:

- if the storage temperature is within -20 and +30°C (-4°F and 86°F): every 6 months,

- if the storage temperature is within -20 and +45°C (-4°F and 113°F): every 3 month.

CAUTION


In case of storage, pay attention to:

modifications reserved

5

User manual GT Series 5/6/8/10 kVA UPS 1.0 (US)