3 INSTALLATION

3.1 TRANSPORT

Transport UPS only in upright position!

The UPS is packaged on a pallet suitable for handling with
a forklift.

Pay attention to the center of gravity.

The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during handling.

Move the UPS in it’s original package to the final
destination site.

Do not stack other packages on top: This could damage
the UPS.

If the UPS must be lifted by crane, use suitable lifting straps
and spreader bars.
Note of the center of gravity marked on the package.

Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS
.

Forklift

Crane

NOTE !

Fig. 3.1-1 UPS cabinets moving

Check for sufficient floor and elevator
loading capacity.


3.1.1 Dimensions and weight

Dimensions SG Series 50 & 80 kVA

(W x D x H)

31.50 x 31.50 x 70.90 inches

800 x 800 x 1,800 mm

S

G

T

5000_0

50-

080_

U

P

S

dim

ens

ions

_G

E

_0

1US

H

D

W

Fig. 3.1.1-1 UPS cabinet dimensions

Weight SG Series 50 & 80 kVA

UPS rating

Weight

Floor loading

lbs/sq.ft / kg/m

2

lbs / kg

SG Series 50 kVA

1,306 / 592

190 / 925

SG Series 80 kVA

1,491 / 676

217 / 1,057

P.S.: Weight including the 5th harmonic filter and EMI filters.

Modifications reserved

Page 10/38

OPM_SGS_ISG_50K_80K_0US_V040.doc

Installation Guide SG Series 50 & 80 kVA