Openings for input and output cable connections

SG

T5

00

0_

05

0-0

80

_U

PS

vie

w t

op

_01

US

31.

50"

800

mm

13.

86"

352

mm

1.18"

30mm

30m

m

1.1

8"

57mm

2.25"

31.50"

800mm

Utility input
Output Load

Battery

Fig. 3.4.1-2 Opening on top of the cabinet for input and output cables

SG Series openings are
provided on the top and the
bottom of the UPS for the
connection of input and
output cables.

Pay attention to the position
of these openings, when
choosing the placement of
the UPS.
These openings are covered
with a protective plate.

SG

T5

00

0_0

50-

08

0_U

PS

vie

w b

ott

om

_02

US

Utility input
Output Load

31.50"

800mm

6.1

0"

155

mm

120mm

4.73"

32mm

1.26"

7.7

6"

197

mm

31.

50"

800

mm

Fig. 3.4.1-3 Opening on the bottom of the cabinet for input and output cables


Positioning of the UPS cabinet
SG Series
is equipped with wheels for easy
placement of the UPS.

To make the UPS movable on wheels, the bolts
on each leg of the cabinet have to be turned
counter-clockwise, until they are free from the
floor and thus the cabinet supported on
wheels.

After having positioned the UPS at its final
location, the cabinet has to be secured by
rotating the bolts on each leg clockwise, but
the wheels must still touch the floor.

To lower

To lift

Fig. 3.4.1-4 Bolts for the regulation of the cabinet

The UPS cabinet is free
standing and normally does
not require to be bolted to
the floor.
The UPS cabinet can be fixed
however to the floor by
bolting it with the supporting
blocks to the floor.
The supporting blocks can be
used in different positions (0°
- 360°)
These supporting blocks are
part of the shipping package.

SGT5

000_050-080_

UPS fixing_01

0 - 360°

See Fig. 3.4.1-5.

Fig. 3.4.1-5 Fixing of the UPS cabinet on the floor

Modifications reserved

Page 13/38

OPM_SGS_ISG_50K_80K_0US_V040.doc

Installation Guide SG Series 50 & 80 kVA