12-1

Data subject to change without notice 7/07. © 2007 GE Drives

The serial interface supports operation, configuration and monitoring of drive functions through an EIA/RS485 connec-
tion. The serial interface is based on Modbus RTU protocol. This protocol allows the drive to function as an RTU slave
on an industrial network.

12.1 Transmission Specification

Item

Specification

Physical level

EIA/RS485

Transmission distance

500 m max.

Number of nodes

32 total

Transmission speed

19200, 9600, 4800, 2400 [bits/s]

Transmission mode

Half duplex

Transmission protocol

Modbus RTU

Character code

Binary

Character length

8 bits

Error check

CRC

12.2 Connection
Connection method

Use shielded wire and connect to the control terminals (DX-, DX+ and SD). A termination resistor should be added
between the data lines on the each end of the network. The value of the termination resistor depends on the character-
istic impedance of the cable. A common value for termination resistors is 120 ohms.

Control terminals

Terminal

marking

Terminal name

Function description

DX+

RS485 communication data (+)

Input/output terminals for RS485

DX-

RS485 communication data (–)

communication.

SD

Cable shield

Electrically floating

12.3 Serial Interface Configuration

Drive function codes H30 to H39 are used to configure the serial interface parameters, such as device address, baud
rate and error response.

12.4 Modbus RTU Functions

The following RTU functions are supported. The maximum number of consecutive parameters for function 03 and 16
messages is 16.

Code

Description

03

Read Holding Registers (16 registers maximum)

06

Preset Single Register

16

Preset Multiple Registers (16 registers maximum)