P:motor parameters, H:high performance functions – GE Industrial Solutions AF-300 P11 User Manual

Page 56

Advertising
background image

5-3

Func.

Factory Setting

Data

Change

No.

Setting Range

Unit

Min.

30 HP

40 HP

Format

during op

C20

JOG frequency

C20

JOG Hz

0.00 to 120.00 Hz

Hz

0.01

5.00

5

Y

C21

PATTERN

(mode select)

C21

PATTERN

0,1,2

-

-

0

1

operation

C22

(Stage 1)

C22

STAGE 1

Operation time: 0.00 to 6000 s

s

0.01

0.00 F1

13

C23

(Stage 2)

C23

STAGE 2

F1 to F4 and R1 to R4

0.00 F1

13

C24

(Stage 3)

C24

STAGE 3

0.00 F1

13

C25

(Stage 4)

C25

STAGE 4

0.00 F1

13

C26

(Stage 5)

C26

STAGE 5

0.00 F1

13

C27

(Stage 6)

C27

STAGE 6

0.00 F1

13

C28

(Stage 7)

C28

STAGE 7

0.00 F1

13

C30

Frequency command 2

C30

FREQ CMD 2

0 to 11

-

-

2

1

N

C31

Offset adjust

(terminal [12])

C31

BIAS 12

-100.0 to +100.0%

%

0.1

0.0

4

Y

C32

(terminal [C1])

C32

GAIN 12

0.0 to +200.0%

%

0.1

100.0

3

Y

5-31

C33

Analog setting signal filter

C33

REF FILTER

0.00 to 5.00s

s

0.01

0.05

5

Y

P:Motor Parameters

P01

Number of motor 1 poles

P01

M1 POLES

2 to 14

-

2

4

9

N

P02

Motor 1

(capacity)

P02

M1-CAP

Up to 30 HP: 0.01 to 60 HP

Hp

0.01

motor capacity

5

40 HP and above: 0.01 to 800 HP

P03

(rated current)

P03

M1-Ir

0.00 to 2000 A

A

0.01

motor rated current

19

N

P04

(tuning)

P04

M1 TUN1

0, 1, 2

-

-

0

21

N

P05

(on-line tuning)

P05

M1 TUN2

0, 1

-

-

0

1

N

P06

(no-load current)

P06

M1-Io

0.00 to 2000 A

A

0.01

standard rated value

19

N

P07

(%R1 setting)

P07

M1-%R1

0.00 to 50.00%

%

0.01

standard rated value

5

Y

P08

(%X setting)

P08

M1-%X

0.00 to 50.00%

%

0.01

standard rated value

5

Y

P09

Slip compensation control

P09

SLIP COMP1

0.00 to 15.00 Hz

Hz

0.01

0.00

5

Y

H:High Performance Functions

H03

Data initializing

H03

DATA INIT

0, 1

-

-

0

1

N

H04

Auto-reset

(times)

H04

AUTO-RESET

0, 1 to 10 times

-

1

0

1

Y

H05

(reset interval)

H05

RESET INT

2 to 20 s

s

1

5

1

Y

H06

Fan stop operation

H06

FAN STOP

0, 1

-

-

0

1

Y

H07

ACC/DEC pattern (mode select)

H07

ACC PTN

0,1,2,3

-

-

0

1

N

H08

Rev. phase sequence lock

H08

REV LOCK

0, 1

-

-

0

1

N

H09

Start mode

H09

START MODE

0, 1, 2

-

--

0

1

N

H10

Energy-saving operation

H10

ENERGY SAV

0, 1

-

-

1

1

Y

H11

DEC mode

H11

DEC MODE

0, 1

-

-

0

1

Y

H12

Instantaneous OC limiting

H12

INST CL

0, 1

-

-

1

1

N

H13

Auto-restart

(restart time)

H13

RESTART t

0.1 to 10.0 s

s

0.1

0.1

0.5

3

N

H14

(freq. fall rate)

H14

FALL RATE

0.00 to 100.00 Hz/s

Hz/s

0.01

10.00

5

H15

(holding DC voltage)

H15

HOLD V

3-phase, 230V class: 200 to 300V

V

1

200V class: 235V

1

3-phase, 460V class: 400 to 600V

400V class: 470V

H16

(OPR command self hold time)

H16

SELFHOLD t

0.0 to 30.0 s, 999

s

0.1

999

3

N

H19

Active drive

H19

AUT RED

0, 1

-

-

0

1

Y

H20

PID control

(mode select)

H20

PID MODE

0, 1, 2

--

-

0

1

N

5-38

H21

(feedback signal)

H21

FB SIGNAL

0, 1, 2, 3

-

-

1

1

N

H22

(P-gain)

H22

P-GAIN

0.01 to 10.00 times

-

0.01

0.1

5

Y

H23

(I-gain)

H23

I-GAIN

0.0, 0.1 to 3600 s

s

0.1

0.0

3

Y

H24

(D-gain)

H24

D-GAIN

0.00 s , 0.01 to 10.0 s

s

0.01

0.00

5

Y

H25

(feedback filter)

H25

FB FILTER

0.0 to 60.0 s

s

0.1

0.5

3

Y

H26

PTC thermistor

(mode select)

H26

PTC MODE

0, 1

0

1

Y

H27

(level)

H27

PTC LEVEL

0.00 to 5.00V

V

0.01

1.60

5

Y

H30

Serial link

(function select)

H30

LINK FUNC

0, 1, 2, 3

-

-

0

1

Y

H31

Modbus-RTU

(address)

H31

ADDRESS

0 (broadcast), 1 to 247

-

1

1

1

N

H32

(mode select on no response error)

H32

MODE ON ER

0, 1, 2, 3

-

-

0

1

Y

H33

(timer)

H33

TIMER

0.0 to 60.0 s

s

-

2.0

3

Y

H34

(baud rate)

H34

BAUD RATE

0, 1, 2, 3

-

-

1

1

Y

H35

(data length)

H35

LENGTH

0 (8-bit fixed)

-

-

0

1

Y

H36

(parity check)

H36

PARITY

0, 1, 2

-

-

0

1

Y

H37

(stop bits)

H37

STOP BITS

0 (2-bit), 1(1-bit)

-

-

0

1

Y

H38

(no response error detection time)

H38

NO RES t

0 (no detection), 1 to 60 s

s

1

0

1

Y

H39

(response interval)

H39

INTERVAL

0.00 to 1.00 s

s

0.01

0.01

5

Y

5-42

5-43

5-39/40

Pg.

5-29

5-29/30

5-30

5-37

5-41

Name

LCD Display

N

N

Y

Y

5-36

5-32

5-33

5-34

5-35