Multi-step frequency selection, Acceleration and deceleration time selection – GE Industrial Solutions AF-300 P11 User Manual

Page 71

Advertising
background image

5-18

E: Extension Terminal Functions

E01 Terminal X1

E09 Terminal X9

E 0 1

X 1

F U N C

E 0 2

X 2

F U N C

E 0 3

X 3

F U N C

E 0 4

X 4

F U N C

E 0 5

X 5

F U N C

E 0 6

X 6

F U N C

E 0 7

X 7

F U N C

E 0 8

X 8

F U N C

E 0 9

X 9

F U N C

Functions can be individually set from each of the digital
input terminals X1 to X9.

Value

Function

0,1,2,3

Multi-step frequency selection (1 to 15 steps)

4,5

Acceleration and deceleration time selection (3 steps)

6

Self-hold selection (HLD)

7

Coast-to-stop command (BX)

8

Alarm reset (RST)

9

External alarm (THR)

10

Jogging (JOG)

11

Frequency setting 2 / Frequency setting 1 (Hz 2 / Hz1)

12

Motor 2 / Motor 1 (M2 / M1)

13

DC injection brake command (DCBRK)

14

Torque limit 2 / Torque limit 1 (TL2 / TL1)

15

Switching operation from line to drive (50 Hz) (SW50)

16

Switching operation from line to drive (60 Hz) (SW60)

17

UP command (UP)

18

DOWN command (DOWN)

19

Edit permission command (WE-KP)

20

PID control cancellation (Hz / PID)

21

Normal/Inverse switching (Terminals 12 and C1) (IVS)

22

Interlock (52-2) (IL)

23

Torque control cancellation (Hz/TRQ)

24

Link communication selection (LE)

25

Universal DI (U-DI)

26

Pick up start mode (STM)

30

Timed alarm stop command (STOP1)

31

Timed alarm stop command with

Deceleration time 4 (STOP2)

Note: Values which are not set in the functions from E01
to E09 are assumed to be inactive.

Multi-step frequency selection

Value 0,1, 2, 3: The frequency can be switched to a
preset frequency in function codes C05 to C19 by
switching the external digital input signal. Assign values
0 to 3 to the target digital input terminal. The combina-
tion of input signals determines the frequency.

3

2

1

0

(SS8)

(SS4)

(SS2)

(SS1)

off

off

off

on

C05 MULTI Hz-1

off

off

on

off

C06 MULTI Hz-2

Related

off

off

on

on

C07 MULTI Hz-3

Functions:

off

on

off

off

C08 MULTI Hz-4

C05-C19

off

on

off

on

C09 MULTI Hz-5

off

on

on

off

C10 MULTI Hz-6

Setting

off

on

on

on

C11 MULTI Hz-7

Setting

on

off

off

off

C12 MULTI Hz-8

0.00 to

on

off

off

on

C13 MULTI Hz-9

- 120.00 Hz

on

off

on

off

C14 MULTI Hz-10

on

off

on

on

C15 MULTI Hz-11

on

on

off

off

C16 MULTI Hz-12

on

on

off

on

C17 MULTI Hz-13

on

on

on

off

C18 MULTI Hz-14

on

on

on

on

C19 MULTI Hz-15

Combination of

Input Signals

Selected Frequency

Acceleration and Deceleration time selection

Value 4, 5: The acceleration and deceleration time can
be switched to a preset time in function codes E10 to
E15 by switching the external digital input signal. Assign
values 4 and 5 to the target digital input terminal. The
combination of input signals determines the acceleration
and deceleration times.

5

4

(RT2)

(RT1)

off

off

F07 ACC TIME1
F08 DEC TIME1

Related

off

on

E10 ACC TIME2

Functions

E11 DEC TIME2

E10-E15

on

off

E12 ACC TIME3

Setting Range

E13 DEC TIME3

0.01 to 3600s

on

on

E14 ACC TIME4
E15 DEC TIME4

Combination

of Input Signals

Selected Acceleration /

Deceleration Times

Advertising