5. Function Selection

5.1 Function Selection List

F: Fundamental Functions

Func.

Unit

Min.

Factory Setting

Data

Change

No.

30 HP

40 HP

Formst

during op

F00

Data protection

F00

DATA PRTC

0, 1

-

-

0

1

N

F01

Frequency command 1

F01

FREQ CMD 1

0 to 11

-

-

0

1

N

F02

Operation method

F02

OPR METHOD

0 to 4

-

-

0

1

N

F03

Maximum frequency 1

F03

MAX Hz-1

50 to 120Hz

Hz

1

60

1

N

F04

Base frequency 1

F04

BASE Hz-1

25 to 120Hz

Hz

1

60

1

N

F05

Rated voltage 1

F05

RATED V-1

0V:

(Output voltage

V

1

230: (230V class)

1

(at Base frequency 1)

proportional to source voltage)

460: (460V class)

230V class:

80 to 240V

460V class:

320 to 480V

F06

Maximum voltage 1

F06

MAX V-1

230V class:

80 to 240V

V

1

230: (230V class)

1

(at Maximum frequency 1)

460V class:

320 to 480V

460: (460V class)

F07

Acceleration time 1

F07

ACC TIME1

0.01 to 3600 s

s

0.01

6.0

20.0

12

F08

Deceleration time 1

F08

DEC TIME1

F09

Torque boost 1

F09

TRQ BOOST1

0.0, 0.1 to 20.0

-

0.1

2.0

12

Y

F10

Electronic

(Select)

F10

ELCTRN OL1

0, 1, 2

-

-

1

3

Y

F11

Thermal 1

(level)

F11

OL LEVEL1

20 to 135% of drive rated current

A

0.01

Motor rated current

1

Y

F12

(time constant)

F12

TIME CNST1

0.5 to 75.0 min

min

0.1

5.0

10.0

19

Y

F13

Electronic thermal overload

F13

DBR OL

[ Up to 15 HP ]

-

-

3

relay (for braking resistor)

0, 1, 2

1

[ 20 HP and above ]

0

F14

Restart mode after

F14

RESTART

0 to 5

-

-

1

momentary power failure

F15

Frequency

(high)

F15

H LIMITER

0 to 120 Hz

Hz

1

70

1

Y

F16

Limiter

(low)

F16

L LIMITER

0

1

N

F17

Gain (for frequency set signal)

F17

FREQ GAIN

0.0 to 200.0%

%

0.1

100.0

1

Y

F18

Bias frequency

F18

FREQ BIAS

-120.0 to +120.0 Hz

Hz

0.1

0.0

1

Y

F20

DC brake

(starting frequency)

F20

DC BRK Hz

0.0 to 60.0 Hz

Hz

0.1

0.0

3

F21

(braking level)

F21

DC BRK LVL

0 to 80%

%

1

0

1

F22

(braking time)

F22

DC BRK t

0.0s (inactive)

s

0.1

0.0

3

F23

Starting frequency

F23

START Hz

0.1 to 60.0 Hz

Hz

0.1

0.5

3

F24

(holding time)

F24

HOLDING t

0.0 to 10.0 s

s

0.1

0.0

3

F25

Stop frequency

F25

STOP Hz

0.1 to 6.0 Hz

Hz

0.1

0.2

1

F26

Motor sound

(carrier freq.)

F26

MTR SOUND

0.75 to 15 kHz (6kHz)

kHz

1

2

1

Y

F27

(sound tone)

F27

SOUND TONE

0 to 3

-

-

0

1

Y

F30

FMA

(voltage adjust)

F30

FMA V-ADJ

0 to 200%

%

1

100

1

Y

F31

(function)

F31

FMA FUNC

0 to 10

-

-

0

1

Y

F33

FMP

(pulse rate)

F33

FMP PULSES

300 to 6000 p/s (full scale)

p/s

1

1440

1

Y

F34

(voltage adjust)

F34

FMP V-ADJ

0%, 1 to 200%

%

1

0

1

Y

F35

(function)

F35

FMP FUNC

0 to 10

-

-

0

1

Y

F36

30RY operation mode

F36

30RY MODE

0, 1

-

-

0

1

Y

F40

Torque limiter1

(driving)

F40

DRV TRQ 1

20 to 150%, 999

%

1

999

1

F41

(braking)

F41

BRK TRQ 1

0%, 20 to 150%, 999

999

1

5-17

F42

Torque vector control 1

F42

TRQVECTOR1

0, 1

-

-

0

1

N

Name

LCD Display

Setting Range

Y

Y

Y

N

N

Y

N

N

0