5-2

E: Terminal Extensions Functions

Pg.

Func.

Factory Setting

Data

Change

No.

Setting Range

Unit

Min.

30 HP

40 HP

Format

During op

E01

X1 terminal function

E01

X1 FUNC

0 to 32

0

1

N

E02

X2 terminal function

E02

X2 FUNC

1

1

N

E03

X3 terminal function

E03

X3 FUNC

2

1

N

E04

X4 terminal function

E04

X4 FUNC

3

1

N

E05

X5 terminal function

E05

X5 FUNC

-

-

4

1

N

E06

X6 terminal function

E06

X6 FUNC

5

1

N

E07

X7 terminal function

E07

X7 FUNC

6

1

N

E08

X8 terminal function

E08

X8 FUNC

7

1

N

E09

X9 terminal function

E09

X9 FUNC

8

1

N

E10

Acceleration time 2

E10

ACC TIME2

0.01 to 3600 s

s

0.01

6.00

20.00

12

Y

E11

Deceleration time 2

E11

DEC TIME2

6.00

20.00

12

Y

E12

Acceleration time 3

E12

ACC TIME3

6.00

20.00

12

Y

E13

Deceleration time 3

E13

DEC TIME3

6.00

20.00

12

Y

E14

Acceleration time 4

E14

ACC TIME4

6.00

20.00

12

Y

E15

Deceleration time 4

E15

DEC TIME4

6.00

20.00

12

Y

E16

Torque limiter 2

(driving)

E16

DRV TRQ 2

20 to 150%, 999

%

1

999

1

Y

E17

(braking)

E17

BRK TRQ 2

0%, 20 to 150%, 999

%

1

999

1

Y

E20

Y1 terminal function

E20

Y1 FUNC

0 to 33

0

1

N

E21

Y2 terminal function

E21

Y2 FUNC

1

1

N

E22

Y3 terminal function

E22

Y3 FUNC

-

-

2

1

N

E23

Y4 terminal function

E23

Y4 FUNC

7

1

N

E24

Y5A, Y5C terminal function

E24

Y5 FUNC

10

1

N

5-24

E25

Y5 RY operation mode

E25

Y5RY MODE

0,1

-

1

0

1

N

E30

FAR function

(Hysteresis)

E30

FAR HYSTR

0.0 to 10.0 Hz

Hz

0.1

2.5

3

Y

E31

FDT function

(level)

E31

FDT1 LEVEL

0 to120 Hz

Hz

1

60

1

E32

signal

(Hysteresis)

E32

FDT1 HYSTR

0.0 to 30.0 Hz

Hz

0.1

1.0

3

E33

OL function

(mode select)

E33

OL1 WARNING

0: Thermal calculation

-

-

0

1

1: Output current

E34

signal (L

(level)

E34

OL1 LEVEL

5 to 150% of rated drive current

A

0.01

motor rated current

19

E35

(timer)

E35

OL1 TIMER

0.1 to 60.0 s

s

0.1

10.0

3

E36

FDT2 function

(level)

E36

FDT2 LEVEL

0 to 120 Hz

Hz

1

60

1

E37

OL2 function

(level)

E37

OL2 LEVEL

5 to 150% of rated drive current

A

0.01

motor rated current

19

E40

Display coefficient A

E40

COEF A

-999.00 to 999.00

-

0.01

0.01

12

E41

Display coefficient B

E41

COEF B

-999.00 to 999.00

-

0.01

0.00

12

Y

E42

LED Display filter

E42

DISPLAY FL

0.0 to 5.0 s

s

0.1

0.5

3

Y

E43

LED Monitor

(function)

E43

LED MNTR

0 to 12

-

-

0

1

Y

E44

(display in STOP mode)

E44

LED MNTR2

0, 1

-

-

0

1

Y

E45

LCD Monitor

(function)

E45

LCD MNTR

0, 1

-

-

0

1

Y

E46

(language)

E46

LANGUAGE

0 to 5

-

-

1

1

Y

E47

(contrast)

E47

CONTRAST

0(soft) to 10(hard)

-

-

5

1

Y

C:Frequency Control Functions

C01

Jump

(Jump freq. 1)

C01

JUMP Hz 1

0 to 120 Hz

Hz

1

0

1

C02

frequency

(Jump freq. 2)

C02

JUMP Hz 2

0

1

C03

(Jump freq. 3)

C03

JUMP Hz 3

0

1

C04

(Hysteresis)

C04

JUMP HYSTR

0 to 30 Hz

Hz

1

3

1

C05

Multistep

(Freq. 1)

C05

MULTI Hz-1

0.00 to 120.00 Hz

Hz

0.01

0.00

5

C06

frequency

(Freq. 2)

C06

MULTI Hz-2

0.00

5

C07

setting

(Freq. 3)

C07

MULTI Hz-3

0.00

5

C08

(Freq. 4)

C08

MULTI Hz-4

0.00

5

C09

(Freq. 5)

C09

MULTI Hz-5

0.00

5

C10

(Freq. 6)

C10

MULTI Hz-6

0.00

5

C11

(Freq. 7)

C11

MULTI Hz-7

0.00

5

C12

(Freq. 8)

C12

MULTI Hz-8

0.00

5

C13

(Freq. 9)

C13

MULTI Hz-9

0.00

5

C14

(Freq. 10)

C14

MULTI Hz-10

0.00

5

C15

(Freq. 11)

C15

MULTI Hz-11

0.00

5

C16

(Freq. 12)

C16

MULTI Hz-12

0.00

5

C17

(Freq. 13)

C17

MULTI Hz-13

0.00

5

C18

(Freq. 14)

C18

MULTI Hz-14

0.00

5

C19

(Freq. 15)

C19

MULTI Hz-15

0.00

5

Y

Y

Y

Name

LCD Display

Y

Y

5-26

5-27

5-28

5-18/21

5-22

5-22/24

5-25