5-20

Edit permission command (data change
permission)(WE-KP) (data protection)

Value 19: This function allows the data to be changed
only when input is received from an external signal,
thereby preventing function code data changes.

19

Selected Function

off

Prohibit data changes

on

Allow data changes

Note: If a terminal is assigned the value 19, the data
cannot be changed. To change data, turn the terminal on
and change its setting to another number.

PID control cancellation (Hz/PID)

Value 20: The PID control can be disabled by an external
digital input signal.

Input Signal

Selected Function

20

[Related Functions: H20-H25]

off

Enable PID control

on

Disable PID control

(When the PID control is disabled, the frequency is set
from keypad panel)

Normal operation/inverse

Value 21: Analog input (Terminals 12 and C1) can be
switched between normal and inverse operations using an
external digital input signal.

Input Signal

Selected Function

21

[Related Function: F01]

off

Normal operation if normal operation is
set and vice versa

on

Inverse operation if normal operation is
set and vice versa

Interlock (52-2)

Value 22: When a contactor is installed on the output side
of the drive, the contactor opens at the time of a momen-
tary power failure. This prevents the reduction of the DC
circuit voltage and may prevent the detection of a power
failure and a correct restart operation after power is
recovered. The restart operation, in the event of a
momentary power failure, can be performed effectively
with power failure information provided by an external
digital input signal.

Torque limit 2/torque limit 1

Value 14: Frequency setting 2/frequency setting 1. This
function switches the torque limit value set with function
codes F40, F41, E16, and E17, using an external digital
input signal.

Input Signal

14

off

F40 DRV TRQ1

Related Functions

F41 BRK TRQ1

F40-F41, E16-E17
Setting Range

on

E16 DRV TRQ2

DRV 20 to 200% ,999

E17 DRV TRQ2

BRK0, 20 to 200%, 999

Selected Torque Limit Value

Switching operation from line drive
(60Hz)(SW60)/(50Hz)(SW50)

Value 15, 16: Motor operation can be switched from 60
Hz/50 Hz commercial power to drive operation without
stopping the motor by switching the external digital input
signal.

Input Signal

Function

16

off > on

Drive operation to line operation (60 Hz)/(50 Hz)

on > off

Line operation to drive operation (60 Hz)/(50 Hz)

Following a momentary power failure, if the digital input
signal goes off, 50 or 60 Hz (according to the input
signal) is output after the restart waiting time (function
code H13). The motor is then directed to drive opera-
tion.

UP command (UP)/DOWN command (DOWN)

Value 17, 18: When an operation command is input (on),
the output frequency can be increased or decreased
using an external digital input signal.

The change ranges from 0 to maximum frequency.
Operation in the opposite direction, of the operation
command is not allowed.

Selected Function
(when operation command is on)

18

17

off

off

Holds the output frequency

off

on

on

off

on

on

Holds the output frequency

Increases the output frequency
according to the acceleration time
Decreases the output frequency
according to the deceleration time

Combination

of Input Signals

There are the two types of UP/DOWN operations as
shown below. Select the desired type by setting the
frequency (F01 or C30).