John Wood Takagi - 110-310-510 User Manual

Page 13

Advertising
background image

13

Vent Termination Clearances

Canada

U.S.A

Direct vent and other

than Direct Vent

Direct

vent

Other than

Direct Vent

A

Clearance above grade, veranda, porch, deck, or balcony.

1 foot

1 foot

1 foot

B Clearance to window or door that may be opened

3 feet

1 foot

4 feet from below or

side opening. 1 foot

from above opening.

C

Clearance to permanently closed window

*

*

*

D

Vertical clearance to ventilated soffit located above the
vent terminator within a horizontal distance of 2 feet
(61cm) from the center line of the terminator.

*

*

*

E

Clearance to unventilated soffit

*

*

*

F

Clearance to outside corner

*

*

*

G

Clearance to inside corner

*

*

*

H

Clearance to each side of center line extended above
meter/regulator assembly

3 feet

*

*

I

Clearance to service regulator vent outlet.

3 feet

*

*

J

Clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other application

3 feet

1 foot

4 feet from below or

side opening. 1 foot

from above opening.

K

Clearance to mechanical air supply inlet.

6 feet

3 feet

3 feet

L

Clearance above paved sidewalk or paved driveway
located on public property.

7 feet

*

7 feet

M

Clearance under veranda, porch deck, or balcony.

1 foot

*

*

* For clearances not specified in CSA B149.1 Natural Gas and Propane Installation Code, please use clearances in

accordance with local installation codes and the requirement of the gas supplier.