Error messages – Burkert Type 8791 User Manual

Page 33

Advertising
background image

33

Operationandfunction

6.7.

error messages

6.7.1.

error messages while the X.TUNE function is running

Display

Cause of fault

remedial action

ERR 1:
No compressed air

No compressed air connected

Connect compressed air

ERR 2:
Compressed air failed
during

X.TUNE

Compressed air failure while the

X.TUNE

function was running

Check compressed air
compressed air supply

ERR 3:
Control system
deaeration side leaking

Actuator or control system deaeration side
leaking

Not possible, device defective

ERR 4:
Control system aeration
side leaking

Control system aeration side leaking

Not possible, device defective

Table 5: Error messages for X.TUNE

English

Software Tool - Positioner

Advertising
This manual is related to the following products: