Cutoff, Sealing function for the positioner – Burkert Type 8791 User Manual

Page 39

Advertising
background image

39

ParameterizationofBasicFunctions

7.2.3.

CUTOFF -
Sealing function for the positioner

This function causes the valve to be sealed outside the control range.

You can enter the limits for the position set-point value here as a percentage. When these limits are reached, the
actuator will be fully deaerated or aerated respectively.

Control mode resumes at a hysteresis of 1%.

Factory setting: close tight low = 2%;

close tight high = 98%

The switching position of the DIP switches in the positioner takes precedence over the communication
software, i.e. settings of the sealing function (

CUTOFF) that are modified through the communication

software are only active if the corresponding DIP switch in the positioner is set to ON.

98

2

%
%

CUTOFF

close tight low
close tight high

Fig. 28: CUTOFF function

Valve stroke [%]

Adjustable from 75 – 100%

Set-point value
[%]

Adjustable from 0 – 25%

Fig. 29: CUTOFF graph