ConfiguringAuxiliaryFunctions

8.5.2.

SPLITRANGE -
Signal Split range

Minimum and maximum values of the input signal as a % for which the valve runs through the entire stroke range.

Factory setting: Lower signal range split = 0%; Upper signal range split = 100%

SPLITRANGE

lower value split range
upper value split range

100

0

%
%

Fig. 36: SPLITRANGE function

Lower value split range: Input the minimum value of the input signal as a %

Adjustment range: 0 – 75%

Upper value split range: Input the maximum value of the input signal as a %

Adjustment range: 25 – 100%

Use this function to limit the position set-point value range of the positioner by specifying a minimum and a
maximum value. This makes it possible to divide a unit signal range that is used (4 – 20 mA, 0 – 20 mA) into
several positioners (without or with overlapping). This allows several valves to be used alternately or, in the case
of overlapping set-point value ranges, simultaneously as actuators.

To split a unit signal range into two set-point value ranges:

Valve stroke [%]

Set-point value [mA]
(

INPUT)

Set-point value range
Positioner 1

Set-point value range
Positioner 2

Fig. 37: SPLTRNG graph