ConfiguringAuxiliaryFunctions

8.5.5.

X.CONTROL -
parameterization of the positioner

Use this function to set the parameters for the positioner (dead band and amplification factors (kp)).

1
1

1.0 %

X.CONTROL

deadband
kp open
kp close

Fig. 42: X.CONTROL menu item

Deadband: Insensitivity range of the positioner

Entry for the deadband as a % in reference to the scaled stroke range;
i.e. X.LIMIT upper stroke limit - X.LIMIT lower stroke (see auxiliary function

X.LIMIT).

This function causes the controller to respond only beginning at a specific control difference. This function saves
wear on the solenoid valves in the positioner and the pneumatic actuator.

If the auxiliary function

X.CONTROL is in the main menu while X.TUNE (Autotune of the positioner) is

running, the deadband is determined automatically depending on the friction behavior of the actuator drive.
The value determined in this way is an approximate value. You can re-adjust it manually.

Position set-
point value

Control
difference

Xd1

Position
actual value

to the
controller

Xd1‘

Dead band

Xd1

Xd1‘

Fig. 43: X.CONTROL graph

Open/close amplification factor: Parameters for the positioner

Open amplification factor:

Amplification factor of the positioner (for closing the valve)

Close amplification factor:

Amplification factor of the positioner (for opening the valve)

English

Software Tool - Positioner