ConfiguringAuxiliaryFunctions

8.5.6.

SAFE.POSITION -
definition of the Safe position

This function specifies the actuator safety position which is approached at defined signals.

The set safety position is only approached if there is a corresponding signal at the binary input (for con-
figuration see

BINARY INPUT) or if a signal error occurs (for configuration see SIGNAL ERROR).

If the mechanical stroke range is limited with the

X.LIMIT function, only safety positions within these limits

can be approached.
This function is executed in AUTOMATIC mode only.

0

%

SAFE POSITION

safety position

Fig. 44: SAFE POSITION function

8.5.7.

SIGNAL.ERROR -
configuration of signal level fault detection

The

SIGNAL ERROR function is used to detect a fault on the input signal.

Fault detection
Fault detection can be selected for a 4 – 20 mA signal only:
Fault if input signal ≤ 3.5 mA (± 0.5% of final value, hysteresis 0.5% of final value)

If 0 – 20 mA is selected, sensor break detection cannot be selected.

SIGNAL ERROR

setpoint error detection

OFF

OFF

ON

Fig. 45: SIGNAL ERROR -1 function

After "setpoint error detection” ON is selected, a new dropdown list appears:

SIGNAL ERROR

setpoint error detection
safety position if setpoint error

ON
OFF

OFF

ON

Fig. 46: SIGNAL ERROR -2 function