ConfiguringAuxiliaryFunctions

8.5.3.

X.LIMIT -
limiting the mechanical Stroke range

This function limits the (physical) stroke to specified % values (lower and upper). In doing so, the stroke range of
the limited stroke is set equal to 100%. If the limited stroke range is left during operation, negative actual posi-
tions or actual positions greater than 100% are shown.

Factory setting: Lower position limit = 0%, upper position limit = 100%

100

0

%
%

X.LIMIT

lower position limit
upper position limit

Fig. 38: X.LIMIT function

Adjustment ranges:

Lower position limit: 0 – 50% of the entire stroke

Upper position limit: 50 – 100% of the entire stroke

The minimum distance between the upper and lower stroke limit is 50%. Therefore if one value is entered with a
minimum distance of < 50% the other value is adjusted automatically.

Limited
stroke

Unlimited
stroke

Physical
stroke (%)

Limited
stroke (%)

Set-point value
[mA] (

INPUT)

Adjustment

range

in

MANUAL

mode

Control

range

in

AUT

OMA

TIC

mode

Fig. 39: X.LIMIT graph