Burkert Type 1094 User Manual

Page 17

Advertising
background image

17

Technical Data

Outputs / Motor contactor

6.5.4.

The output for the motor contactor is activated by the controller for as
long as the proportional valve is open.
This contactor/relay switches the vacuum pump motor.
Furthermore, a overtravel time can be set for the vacuum pump (motor
contactor) for which the signal remains active. If the overtravel is set
to 0s, the motor contactor is not activated. This function is useful for
defective motors.

Load current:

0 ... 150 mA

Output voltage:

24 V DC

Number of outputs: 2 (1 output each for side 1 and for side 2)

Output

µController

24 V

Connection
terminals
for motor
contactor

GND

Motor contact output of the controller Type 1094 EV

Fig. 7:

Operation as ac device at 230/115 V

6.5.5.

A power supply unit was installed for the operation of the vapor
recovery 1094 EV. This power supply unit has the following data:
Manufacturer:

TRACO POWER

Designation:

Industrial Power Supply

Model:

TBL 030-124

Power supply voltage:

100 ... 240 V 50/60 Hz -15 % / +10 %

Max. power consumption: 0,5 ... 0,9 A
Output voltage:

24 V DC ±10 %

Max. output current:

1.25 A

Max. output power:

30 W

Control Type 1094 EV with 24 V power supply unit

Fig. 8:

English

Type 1094 EV