36

Pin 4: CAN_H

Pin 5: CAN_L

Pin 1: Drain

Pin 3: V–

Pin 2: V+

View of plug from the front onto the pins:

Pin

Signal Color

1

Drain

(shield)

2

V+

red

3

V-

black

4

CAN_H

white

5

CAN_L

blue

An external initiator can be
connected using the small
3-pin terminal strip - see
manual, chapter „Connection
of an external initiator“
.

english

37

Network Topology

11.6.

When installing a DeviceNet system, ensure that the termi-
nating circuit of the data lines is correct. The circuit prevents
the occurrence of interference caused by signals refl ected
onto the data lines.

The trunk line must be terminated at both ends with
resistors of 120

Ω

and 1/4 W power loss (see the manual,

chapter „Network Topology of a DeviceNet System“).

Confi guring the Baud rate

11.7.

and DVN address

8 DIP switches are available for confi guration:

DIP switches 1 to 6

for DeviceNet address

(factory setting:

63, i.e. DIP 1 - 6: on)

DIP switches 7 to 8

for Baud rate

(factory setting:

125, i.e. DIP 7 + 8: off)

Further confi guring - see manual, chapter „Confi guring the
DeviceNet address / baud rate“

english

38

Confi guration of Process Data

11.8.

To transmit process data via an I/O connection, 2 static
input and 1 static output assembly can be selected, see
manual, chapter “Confi guration of Process Data

„Address“ in the table describes the data attribute of the
assemblies for read access (class, instance, attributes).

Input-
Assemblies

Address

Format of the Data attribute
value 0: OFF / value 1: ON

S1…S4

(factory
setting)

4, 1, 3

Byte 0:
Bit 0: position S1
Bit 1: position S2
Bit 2: position S3
Bit 3: position S4

S1…S4 +
POS

(with POS:
current
position)

4, 2, 3

Byte 0:
Bit 0: position S1
Bit 1: position S2
Bit 2: position S3
Bit 3: position S4
Bit 4…7: not used

Byte 1:
POS in mm

„Address“ in the table describes the data attribute of the
assemblies for read access (class, instance, attributes).

english

39

Output-
Assembly

Address

Format of the Data attribute
value 0: OFF / value 1: ON

Solenoid
valve
SV 1 ... 3

4, 21, 3

Byte 0:
Bit 0: SV1
Bit 1: SV2
Bit 2: SV3
Bit 3…7: not used

Confi guration of the Safety

11.9.

Position of Solenoid Valves if
Bus Error

If the bus fails, the solenoid valve is switched to a program-
mable safety position (factory setting: the solenoid valve
is in the power-off-state) - for details see manual, chapter
„Confi guration of the device“.

The bus status LED „Network“ on the electronic module
specifi es the kind of error by color and blinking pattern - for
details see manual, chapter „Display of the Status LEDs in
the event of a bus error
“).