24

Cable gland with Multi-pole connection:

Internal cabling work is not required for models with multi-pole
connection. But you will require the correspondingly
assembled cable sets with the following pin assignments:

Pin

Description

Confi guration

1

24 V

Power supply 24 V

2

GND

GND

3

S1 OUT

Output position 1

4

S2 OUT

Output position 2

5

S3 OUT

Output position 3
(Option: analog signal)

6

S4 OUT

Output external initiator

7

Y1

Input solenoid valve 1

8

Y2

Input solenoid valve 2

9

Y3

Input solenoid valve 3

10-12

not used

An external initiator can be connected using the small 3-pin
terminal strip 2 (see fi gure on page 22 or manual, chapter
„Connection of an external initiator“).

english

25

Input and output signals to the higher-level control (PLC):

Pin 9 - Y3

Pin 8 - Y2

12

Pin 6 - S4 out

Pin 7 - Y1

Pin 1 - 24 V

Pin 5 - S3 out

Pin 4 - S2 out

11

Pin 3 - S1 out

Pin 2 - GND

10

(12-pole circular plug-in connector M12 x 0.75 - male,
acc. to IEC 61076-2-101 — view onto the plug pins)

english

26

10.

AS-I - DESIGN

Connection options

10.1.

left connection:
1 x M16 x 1,5 cable gland with Multi-pole connection
(M12 plug according to IEC 61076-2-101, 4-pole) on a
cable of 8 or 80 cm length

right connection:
1 x M16 x 1,5 cable gland for external initiator

Maximum Length of the Bus

10.2.

Line

The bus cable may be a maximum of 100 m long. When
designing the system, consider the length of the round cable
leading directly to the control head (see example calculation
in the operating instructions).

english

27

Number of Connectable

10.3.

Control Heads

In AS interface versions with extended addressing range
(A/B slave), 1 master can communicate with 62 slaves.

In AS interface versions with addressing range 31 slaves a
maximum of 31 control heads can be connected to a bus line
(the address range restriction).

10.4.

Electrical Data

Power supply:

Standard: via AS-i
(29,5 ... 31,6 V DC
acc. specifi cation)

Option: externally

(19,2 V DC to 31,6 V DC)

Setting the valve’s power supply using jumpers on the
AS-interface electronics module.

Input / proximity switches (external initiator: S4 in):
Power supply:

AS interface voltage present at

control head - 10 %