Burkert Type 8681 User Manual

Page 6

Advertising
background image

20

Electrical Data

9.2.

Power supply:

12 ... 28 V DC, residual ripple 10 %

Power consumption:
(standby current):

30 mA at 24 V DC

Solenoid valves:
Power input per max. 0.8 W
solenoid valve:

(0.9 W during activation)

Operating mode: Long-term operation (100 %)

Central display of the
switching states:

42 mA with a power supply of
24 V DC per illuminated display;

Outputs/binary
feedback signals:

S1 out - S4 out

Design:

Normally open contact, PNP output

short-circuit-proof, with self-clocking

short-circuit

protection

Switchable
output current:

max. 100 mA per feedback signal

Option: Analog feedback signal:
Signal output:

S3 out (binary feedback signal

S3out not available)

Type:

Current source (4 to 20 mA)

english

21

Input / proximity switches (external initiator: S4 in):
Power supply:

Voltage present at control head - 10 %

Current carrying
capacity, sensor
power supply:

max. 90 mA;

short-circuit

protection

Design:

DC 2- and 3-conductor, NO or NC

(factory setting NO), PNP output

Valve control inputs (Y1 - Y3):
Signal level - active: U > 10 V, max. 24 V DC + 10 %

Electrical Installation

9.3.

(24 VDC)

WARNING!

Risk of injury due to electrical shock!

Before reaching into the system (except for the

Teach-In procedure in a non-explosive atmosphere)
switch off the power supply and secure it to prevent
restarting!
Observe applicable accident prevention and safety

regulations for electrical equipment!

Risk of injury from improper installation!

Installation may be carried out by authorized techni-

cians only and with the appropriate tools!

english

22

Cable glands:

Open the housing.

Assemble connection cables for signals and power

supply as well as for the external initiator.

Insert cables through the respective cable glands into

the interior of the housing.

Secure the wires to the terminal strips according to the
pin assignments depicted in the fi gure.

Solenoid valve

connection

with status

LED for SV1

Terminal strip 1

Service
interface

DIP switches
for color
coding the
LED‘s

Terminal strip 2
(for external
initiator)

Teach-In-
buttons T1-3

SV-connections
with status LED
for SV2, 3

english

23

Terminal strip 1

Confi guration

24 V

Power supply 24 V

GND

GND

S1 OUT

Output position 1

S2 OUT

Output position 2

S3 OUT

Output position 3
(Option: analog signal)

S4 OUT

Output external initiator

Y1

Input solenoid valve 1

Y2

Input solenoid valve 2

Y3

Input solenoid valve 3

Terminal strip 2

Confi guration

24 V

Power supply 24 V for external
initiator

S4 IN

Input external initiator

GND

GND external initiator

Close the housing

.

Ensure IP protection

(dummy plugs)!

english

Type 8681

Advertising