Current carrying capacity,
sensor power supply: max. 30 mA;
short-circuit

protection

Design:

DC 2- and 3-conductor, NO or
NC (factory setting NO), PNP
output

Inputs (from master
perspective):

3 binary feedback signals and
external initiator

Outputs (from master
perspective):

0 to 3 solenoid valves

Switching capacity: max. 0.8 W via AS interface
Pull-in current:

30 mA or 0.9 W / 200 ms

Operating mode:

Long-term operation (100 %)

Central display of the switching states:
Power consumption: max. 33 mA or 1 W per illumi-

nated display (at 30.5 V AS-

interface

voltage)

Power supply via AS interface bus:
Power consumption
from AS interface:

max. 200 mA (incl. external

initiator with 30 mA)

Integrated short-circuit protection

english

29

External Power Supply:
Ext. power supply:

19.2 V DC to 31.6 V DC

Max. power consumption

from external power supply:

 110 mA at 24 V DC

Integrated short-circuit protection

Electrical Installation (AS-i)

10.5.

WARNING!

Risk of injury due to electrical shock!

Before reaching into the system (except for the

Teach-In procedure in a non-explosive atmosphere)
switch off the power supply and secure it to prevent
restarting!
Observe applicable accident prevention and safety

regulations for electrical equipment!

Risk of injury from improper installation!

Installation may be carried out by authorized techni-

cians only and with the appropriate tools!

Internal cabling work is not required for any of the AS Interface
designs with multi-pole connection. However, you will require
the correspondingly assembled cable sets with the following
pin assignments.

english

30

Pin 2

Pin 3

Pin 1

Pin 4

Likewise, the jumpers on the electronics module must be set
correspondingly (power supply via AS-i or externally) - see
page 27 .

Power supply

Pin

(via AS-i)

Confi guration

(externally)

Confi guration

Color

1

AS-i+

AS-i+

brown

2

not used

GND

white

3

AS-i-

AS-i-

blue

4

not used

24 V+

black

An external initiator can be connected using the small
3-pin terminal strip 2 - see manual, chapter „Connection of
an external initiator“
.

english

31

11.

DEVICENET- DESIGN

Connection

11.1.

left connection:
1 x M16 x 1,5 cable gland with Multi-pole connection
(M12 plug according to IEC 61076-2-101, 5-pole) on a
cable of 80 cm length

right connection:
1 x M16 x 1,5 cable gland for external initiator

DeviceNet Specifi cation

11.2.

EDS fi le

8681.EDS

Icons 8681.ICO

Baud rate

Factory setting: 125 kBit/s

Address

Factory setting: 63

english

Type 8681