Table 5-9. Controller Modules (CON0-3)

Title

Definition

Atom

CON0

CON1

CON2

CON3

Default

Auto Status

When Output Track Status (OVTS) is

0, 1

indicates Control Output (CO) is selected as
the output.

0 indicates the output comes from

the output push buttons.

AUT

(0-3)

L107

L131

L155

L179

0

Remote Status

When the Setpoint Track Status (SPTS) is

0, 1

indicates the setpoint is derived from the
Remote Setpoint (RSP).

0 indicates it comes

from the setpoint push buttons.

RMT
(0-3)

L108

L132

L156

L180

0

Reverse Valve

This parameter specifies the location of
Open/Close indicators in the control display.
1 means that 20 mA closes the valve. 0
indicates that 20 mA opens the valve.

RSV

(0-3)

L109

L133

L157

L181

0

Alarm A Active

See Control Alarm Mode (AIX).

PA1

(0-3)

L110

L134

L158

L182

0

Alarm B Active

See Control Alarm Mode (AIX).

PA2

(0-3)

L111

L135

L159

L183

0

Auto Switch

This parameter is used in conjunction with
Auto Enable (AE) to allow the Control Output
(OUT) to become the auto/manual generator
result Output (OUT).

SWA

(0-3)

L112

L136

L160

L184

0

Remote Switch

This parameter is used in conjunction with
Remote Setpoint Enable (RE) to allow the
modified Remote Setpoint to become the
setpoint value to the setpoint generator.

SWR

(0-3)

L113

L137

L161

L185

0

Auto Enable

When this parameter is set to a

1, the Control

Output (CO) becomes the auto/manual
generator result Output (OUT) if the Auto
Switch (SWA) is set to a

1 by the A/M push

button or user program (F-TRAN, FCIM, or
FCS wire list).

AE

(0-3)

L114

L138

L162

L186

1