Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual

Page 287

Advertising
background image

Table 15-3. CS41 Four Loop Controller Datapoints

Data-

point

Table

Module

Title and Function

De-

fault

AI5 - Process Variable Loop 4 (Cont)

L421

5-4

AI5

0-5 V Input - Enter a value that matches the signal voltage
range of the Loop 4 PV transducer. 1 = 0 - 5 V range; 0 = 1 -
5 V range.

0

L445

5-4

AI5

Square Root Signal - It is used if the Loop 4 PV transducer is
a nonlinear differential pressure (DP) cell that provides a
squared signal value. 0 = input is already linear; 1 = square
root to restore linearization.

0

AI6 - Remote Setpoint Loop 3 (Is affected by Setpoint Related Datapoints)

L163

5-9

CON2

Remote Setpoint Enable - This datapoint is controlled by
CCI2. When CCI2 is a closed contact, this datapoint is set to
1 to allow the modified Loop 3 Remote Setpoint to become
the value used as the control setpoint if the R/L push button
is in Remote.

0

C184

5-9

CON1

Remote Setpoint Bias (B1) - This datapoint and Remote
Setpoint Ratio (K1) allow the Remote Setpoint input to be
modified by the Setpoint Generator.
Setpoint = [Remote Setpoint X Ratio] + Bias
SP = [RSP X K1] + B1
The B1 and K1 datapoints are modified when the input signal
must be scaled to match the setpoint range desired.

0

C185

5-9

CON1

Remote Setpoint Ratio (K1) - See Remote Setpoint bias (B1)
above.

1

C262

5-4

AI6

Engineering Span - Set to 100 by CS41; however, it can be
changed. Enter a value, that when added to Engineering
Zero, will produce an upper range value in engineering units
that represents the Loop 3 Remote Setpoint upper range
signal value.

100

(CS41)

C282

5-4

AI6

Engineering Zero - Enter a value that represents in
engineering units the Loop 3 Remote Setpoint lower range
signal value.

0

B275

5-4

AI6

Digital Filter Index - This is a first order filter that can be
applied to the Loop 3 Remote Setpoint signal. See Table 5-4
for input values.

3

L422

5-4

AI6

0-5 V Input - Enter a value that matches the signal voltage
range of the Loop 3 Remote Setpoint signal. 1 = 0 - 5 V
input range; 0 = 1 - 5 V input range.

0

L446

5-4

AI6

Square Root Signal - It is used if the Loop 3 Remote Setpoint
input is a squared signal value that must be linearized. 0 =
input is already linear; 1 = square root to restore linearization.

0

4 of 13

53MC5000 Process Control Station

15-12

Advertising