Step

Procedure

1

Press the

F2 push button and DO NOT RELEASE IT.

2

While the

F2 push button is still held pressed, use a paper clip to press the

reset button. DO NOT RELEASE the

F2 push button.

3

The display goes all black and then the default display appears.

4

Release the

F2 push button. (The database is reset to the default values with

the default display present on the controller.)

If the

F3 push button is held pressed during controller reset, the controller is forced to FIX 0,

Suspend Control State. In FIX 0 the control program stops, inputs continue to be measured,
and totalizers and trends continue to update. Outputs reflect the contents of their associ-
ated datapoints. The logo appears on the display. Use the same proce-
dure provided in the table above (press the

F3 instead of F2).

18.7 SUPPLEMENTAL INFORMATION

Schematics and pin assignment illustrations are provided as follows:

Backplane:

Figure 18-2. Hand Held Configurer and Valve Holder Pin Assignments

Figure 18-3. Cord Set Connector Pin Assignments

Interconnection Terminal Boards (ITBs):

Figure 18-4. Cord Set ITB Schematic

Figure 18-5. Dual Relay ITB Schematic

Figure 18-6. 6 Digital Input/4 Digital Output (6DI/4DO) ITB Schematic

Figure 18-7. 16 Digital Input/Digital Output (16DI/DO) ITB Schematic

Figure 18-8. Analog ITB Schematic

Figure 18-9. Communication ITB Schematic

Expansion Board Option Cards:

Figure 18-10. 6 Digital Input/4 Digital Output (6DI/4DO) PCB Option

Figure 18-11. 16 Digital Input/Digital Output (16DI/DO) PCB Option

Figure 18-12. Single Channel Analog Input PCB Option

Figure 18-13. Multi I/O Analog PCB Option

Figure 18-14. High Speed Communications PCB Option

Section 18. Maintenance and Parts List

18-13