Table 13-3. CS22 Two Loop Override Controller Datapoints

Data-

point

Table

Module

Title and Function

Default

AI3 - Remote Setpoint Limiting (Is affected by Setpoint Related Datapoints) (Cont)

B272

5-4

AI3

Digital Filter Index - This is a first order filter that can be
applied to the Limiting Variable Loop Remote Setpoint
signal. See Table 5-4 for input values.

3

L419

5-4

AI3

0-5 V Input - Enter a value that matches the signal voltage
range of the Limiting Variable Loop Remote Setpoint signal.
1 = 0 - 5 V input range; 0 = 1 - 5 V input range.

0

L443

5-4

AI3

Square Root Signal - It is used if the Limiting Variable Loop
Remote Setpoint input is a squared signal value that must
be linearized. 0 = input is already linear; 1 = square root to
restore linearization.

0

AO0 - Control Output Limiting (Primary, Limiting)

L472

5-5

AO0

0-20 mA Output - 0 = 4-20 mA signal; 1 = 0-20 mA signal.
Enter a value to match the output valve requirements.

0

L120,
L144

5-9

CON0,
CON1

Manual Fallback Disable - 0 = always power up in manual; 1
= auto/manual selector unchanged at power up.

0

L122,
L146

5-9

CON0,
CON1

Hard Manual Limit - 1 = apply output limits to the final output
of the Auto-Manual generator. Affects both the manual push
buttons and the controller’s result. 0 = do not apply limits.

1

C109
C145

5-9

CON0,
CON1

Output High Limit - Sets maximum Control Output Limiting
signal value for in engineering units.

100

C110,
C146

5-9

CON0,
CON1

Output Low Limit - Sets minimum Control Output Limiting
signal value in engineering units.

0

C118,
C154

5-9

CON0,
CON1

Output Slew Rate - It is a rate limit applied to the output
value. When configured to a non-zero value, the output
from the Auto-Selector is only allowed to change by this
amount each scan time. A zero disables output slewing. It
does not affect manual operation.

0

CON0 Control Related Datapoints

C106

5-9

CON0

Proportional Band - Is the percent of error required to move
the output full scale for proportional action.

100

C107

5-9

CON0

Reset Time - Is the number of minutes per repeat of integral
action. It is mutually exclusive with Manual Reset.

0

C108

5-9

CON0

Rate Time - Represents the minutes proportional action is
advanced.

0

C111

5-9

CON0

Manual Reset - It determines the output valve position when
the controller is in Auto and the error = 0. It is mutually
exclusive with Reset Time.

50

L106

5-9

CON0

Reverse Switch - 0 = Control Output Limiting

if Primary

Variable

; 1 = Control Output Limiting

if Primary

Variable

.

1

L114

5-9

CON0

Auto Enable - Controller output is from a PID algorithm when
set to 1 and A/M push button is in Auto.

1

C115

5-9

CON0

Controller Span - Enter a value, that when added to the
Primary Controller Lower Range value, will produce the
control upper range value in engineering units.

100