Table 1-5. OPTO 22 Module Specifications for 16DI/DO ITB

OPTO 22 DC Input Modules (Cont)

OPTO 22

Part Number

16DI/DO

Voltage

Input Voltage Range

Input

Current @

Max V In

Input

Maximum

for No Output

G41DC5G

5 V dc

35 - 60 V dc

6 mA

9 V dc

G41AC5

5 V dc

90 - 140 V dc

11 mA

45 V dc

G41AC5A

5 V dc

180 - 280 V dc

6.5 mA

80 V dc

G41DC24

24 V dc

10 - 32 V dc

25 mA

3 V dc

G41AC24

24 V dc

90 - 140 V dc

11 mA

45 V dc

OPTO 22 DC Output Modules

OPTO 22

Part Number

16DI/DO

Voltage

Output Line

Voltage

Range

Load

Current

@ 45

°

C

Load

Current

@ 70

°

C

Maximum

Off State

Leakage

G40DC5

5 V dc

5 - 60 V dc

3 Amps

2 Amps

1 mA

G40DC5A

5 V dc

5 - 200 V dc

1 Amp

0.55 Amp

2 mA

G40DC24

24 V dc

5 - 60 V dc

3 Amps

2 Amps

1 mA

Table 1-6. Single Channel Analog Input Option (AI8) Specifications

Item

Specification(s)

This option requires one of the 5B series isolation modules described in Table 1-8.

Safety classification

FM Approved: Nonincendive for Class 1, Div. 2, Group A,
B, C, & D hazardous locations.

Quantity

1 (Analog Input 8 - AI8).

Analog-to-digital specifications:
Accuracy
Resolution

±

0.1% Full Scale

12 bits

2 of 2

Section 1. Introduction

1-17