17.5 MODIFICATIONS TO TUNING CRITERIA

During EASY-TUNE sequence execution, each of the three algorithm variables: Time Constant
(T

P

), Process Gain (K

P

),

and Dead-Time (W

P

) are altered by 10% in the

conservative direction

(controller operating characteristics would be slower response, but less chance of oscillation and
instability) before the tuning parameters are computed using the ITAE equations listed in Table
17-5. (Figure 17-2 illustrates the equation variables with respect to the response curve.) The
three variables

T

p

, K

P

, and W

P

can be increased numerically to compute tuning parameters that

are more conservative or decreased for

less conservative tuning parameter calculations (controller

operating characteristics would be faster response and greater chance of instability or oscillation).
Parameters used to alter the variables are the EASY-TUNE Modifiers, datapoints C382 (T

P

Modi-

fier), C383 (D

P

Modifier), and C384 (W

P

Modifier). It is recommended that the values entered in

C382, C383, and C384 be between -0.5 and 0.5. The effect on the equation variables is as follows:

T

P

modified = T

P

(1 - C382)

K

P

modified = K

P

(1+ C383)

W

P

modified = W

P

(1+ C384)

Table 17-5. EASY-TUNE Equations

Mode

PB in %

TR (Minutes)

TD* (Minutes)

P

204K

P

(W

P

/T

P

)

1.084

0

0

PI

116.4K

P

(W

P

/T

P

)

0.977

(T

P

/40.44)(W

P

/T

P

)

0.68

0

PID

73.69K

P

(W

P

/T

P

)

0.947

(T

P

/51.02)(W

P

/T

P

)

0.738

(T

P

/157.5)(W

P

/T

P

)

0.995

PD**

54.02K

P

(W

P

/T

P

)

0.947

0

(T

P

/157.5)(W

P

/T

P

)

0.995

I**

0

T

P

[(K

P

/25)(W

P

/T

P

)

0.15

]

0

Note: Process characteristics T

P

, K

P

, and W

P

are used to compute the ideal tuning parameters

aDOrding to the Minimum Integral of Absolute Error Multiplied by Time Criterion (ITAE) for P, PI,
and PID modes.

*If computed to be < B003/50, then T

D

= 0.

**Empirical estimates, not based on ITAE method.