Table 5-14. system module – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual

Page 183

Advertising
background image

Table 5-14. System Module

Title

Definition

Atom

Data-

point

De-

fault

Parameter
Modify

Enable Tuning Parameter Limits
0 - no limits checked, 1 - limits below apply

C385 lowest % PB
C386 highest % PB
C387 lowest T

R

(minutes)

C388 highest T

R

(minutes)

C389 lowest T

D

(minutes)

C390 highest T

D

(minutes)

PLIM

L520

1

Automatic
Tuning
Parameter
Entry

Automatic Tuning Parameter
1 - upon successful completion of the EASY-TUNE sequence,
new tuning parameters will be entered.
0 - new tuning parameters will not be entered but available for review.

APLD

L522

0

Status

This parameter presents the state of the EZ-TUNE procedure or, when a failure occurs, the error
condition code as shown below:

EASY-TUNE Normal Successful Status Display
B387 =

Description

1

Settling time & finding initial steady-state values

2

Initial step disturbance to the process

3

Preliminary process characterization (Disturbance is removed)

4

Finding second steady-state values (Disturbance is re-applied)

5

Finding process characteristics (Disturbance is removed)

0

EASY-TUNE has successfully completed

ESTAT

B387

0

5-
3

8

53
MC

50
00
Pr
o

c

ess Co

nt

ro

l Sta

tio

n

Advertising