INSTALLATION DIAGRAMS

A copy of each of the following interconnection diagrams is included in this Appendix.

In Class I, Division 2 installations these drawings shall be used in place of the installation drawings
provided in the 53MC5000 Instruction Manual and 53MC5000 Quick Start Installation Guide.

ID-53-1592

Installation Diagram, Standard Rear Terminal Board and Expansion
Rear Terminal Board

ID-53-1593

Installation Diagram, Discrete ITB and Dual Relay ITB

ID-53-1594

Installation Diagram, Cord Set Rear Terminal Board and Expansion
Rear Terminal Board

ID-53-1595

Installation Diagram, Cord Set ITB and Dual Relay ITB

ID-53-1596

Installation Diagram, Analog ITB

ID-53-1597

Installation Diagram, MicroLink Communications

ID-53-1598

Installation Diagram, Standard Communications with Cord Set

ID-53-1599

Installation Diagram, Standard Communications with Standard Rear Ter-
minal Board

ID-53-1601

Installation Diagram, Controller to SCADA Adaptor

ID-53-1603

Installation Diagram, 16DI/DO ITB

CORRECTIVE MAINTENANCE

WARNING

EXPLOSION HAZARD, DO NOT DISCONNECT CABLES, MODULES, OR

FUSES UNLESS POWER HAS BEEN DISCONNECTED OR THE AREA IS

KNOWN TO BE NON-HAZARDOUS.

When the equipment is installed in a Class I, Division 2 location, no service that requires the removal,
replacement, or connection of components or wiring shall be performed on any circuits not known to
be operating at intrinsically safe energy levels unless the power supplies have been disconnected or
the area is known to be nonhazardous. If the area is to be declared nonhazardous, it is the user’s
responsibility to determine whether the atmosphere is hazardous with a suitable combustible gas
detector.