13.2 CS22 CONTROL SIGNALS

Loading CS22 connects the 53MC5000 Controller function blocks for operation as two standard
PID controllers. As shown in Figure 13-1, CS22 provides ten control signals which are described
in Table 13-1.

Table 13-1. CS22 Control Signals

Control

Signal

Definition

Cord

Set

ITB

Rear

Term

Board

Signal

AI0 - Primary
Variable Loop

This analog input signal represents the value of
the primary loop process to be manipulated by
the controller. It is compared to the primary
setpoint to determine the Primary Variable Loop
value that is compared to the Limiting Variable
Loop value for control of the final element.

TB1-1 (+)
TB1-2 (-)
TB1-3

1 (+)
2 (-)
3

+24 V
AI0
SC

AI1 - Remote
Setpoint
Primary

This analog input signal represents the value to
be used as the primary setpoint when remote
setpoint operation is selected with the faceplate
push buttons and enabled by DI0.

TB1-5 (+)
TB1-6 (-)
TB1-7

4 (+)
5 (-)
6

+24 V
AI1
SC

AI2 - Limiting
Variable Loop

This analog input signal represents the value of
the limiting loop process to be manipulated by
the controller. It is compared to the limiting
setpoint to determine the Limiting Variable Loop
value that is compared to the Primary Variable
Loop value for control of the final element.

TB1-9
TB1-10 (+)
TB1-11 (-)

1
7 (+)
8 (-)

+24 V
AI2
SC

AI3 - Remote
Setpoint
Limiting

This analog input signal represents the value to
be used as the limiting setpoint when remote
setpoint operation is selected with the faceplate
push buttons and enabled by DI1.

TB1-13
TB1-14 (+)
TB1-15 (-)

4
9 (+)
8 (-)

+24 V
AI3
SC

AO0 - Control
Output Limiting

This is the 4-20 mA output signal that drives the
final control element.

TB1-17 (+)
TB1-18 (-)

10 (+)
11 (-)

AO0
PC

AO1 - Override
Status

This signal indicates which one of the two loops
is driving the final control element. When
control is from the primary loop, output is 4 mA;
when control is from the limiting loop, output is
20 mA.

TB1-19 (+)
TB1-20 (-)

12 (+)
11 (-)

AN01
PC

DI0 - Remote
Enable Primary

When a closed contact is present on this input,
the operator can select the setpoint value to be
set by the value of the Remote Setpoint Primary
input with the R/L push button.

TB2-1 (+)
TB2-2 (-)

13 (+)
14 (-)

DI0
PC

DI1 - Remote
Enable Limiting

When a closed contact is present on this input,
the operator can select the setpoint value to be
set by the value of the Remote Setpoint Limiting
input with the R/L push button.

TB2-3 (+)
TB2-4 (-)

15 (+)
14 (-)

DI1
PC

DO0 - Process
Alarms Primary

This contact is closed when the Primary
Variable value is not within the C103 and C104
datapoint values (Loop 1 Alarm Limits 1 and 2);
otherwise, the contact is open.

TB2-5 (+)
TB2-6 (-)

16 (+)
17 (-)

DO0
PC

1 of 2

53MC5000 Process Control Station