2 - Electrical connections

PRECAUTIONS

B

Despite the fact that the instrument
has been designed to work in an
harsh and noisy environmental
(level IV of the industrial standard
IEC 801-4), it is strongly recom-
mended to follow the following
suggestions.

A

All the wiring must comply with the
local regulations.

The supply wiring should be rout-
ed away from the power cables.
Avoid to use electromagnetic con-
tactors, power relays and high
power motors nearby.
Avoid power units nearby, espe-
cially if controlled in phase angle

Keep the low level sensor input
wires away from the power lines
and the output cables.
If this is not achievable, use shield-
ed cables on the sensor input, with
the shield connected to earth.

2.2 RECOMMENDED ROUTING OF WIRES

B

1

2

3

4

5

6

7

8

9

10

11

12

L

N

IN

Conduit for supply and output cables

Conduit for low level sensor cables

A

B

D

E

C

1

2

3

4

5

6

7

8

9

10

11

12

L

N

IN

A

B

D

E

C

A = Supply
B = Outputs
C = Analog inputs
D = Analogue output

Serial communications

E = SSR drive output